Glanded Pumps - THERMO-ECO-ENGINEERING úvod
Glanded Pumps - THERMO-ECO-ENGINEERING úvod
Glanded Pumps - THERMO-ECO-ENGINEERING úvod
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Pump Management Systems Wilo-Control<br />
Pump Control<br />
Planning Guide<br />
LON is an open, non-manufacturer-specific system which enables<br />
open, intersectional communication between different components<br />
and systems. It thus offers advantages to planner, installer and operator,<br />
such as:<br />
• Intersectional trade integration<br />
• Non-manufacturer-specific<br />
• Creation of functional added values<br />
• Avoidance of installation and planning errors thanks to a standardised<br />
data interface (prerequisite: no changing transfer media)<br />
• Reduction of installation expenditure in comparison with standalone<br />
systems<br />
• Reduced investment costs through multiple utilisation of sensors<br />
• No expensive gateway solutions are required for data communication<br />
between stand-alone systems<br />
• Flexibility in the event of modifications and retrofitting<br />
• Reduced operating costs thanks to intelligent energy management<br />
• Efficiency and operational reliability due to hydraulic load management<br />
in heating / ventilation / air-conditioning installations<br />
• Overall transparency due to centralised displays, interventions and<br />
monitoring<br />
• Standardised and transparent operation of equipment and buildingservices<br />
systems<br />
• LONWORKS provides for 2 directions of communication:<br />
• Vertical communication between components on the field level and<br />
automation stations on the automation level<br />
• Horizontal communication between components at the field level<br />
It is horizontal communication in particular which allows the set-up<br />
of decentralised structures which operate without higher-level automation<br />
stations. It has thus become possible to realise previously<br />
expensive control tasks with significantly lower installation expenditure;<br />
e.g. a controlled pump with communication capability can<br />
exchange data directly via LON with a valve, a differential-pressure<br />
sensor or a boiler control system and undertake control tasks. In parallel<br />
fashion, the pump can send electrical and hydraulic operating<br />
data for statistical conditioning and if necessary fault and run /<br />
process signals to the higher-level control room and receive higherlevel<br />
commands from this control room.<br />
Communication takes place with the standardised LONTALK protocol<br />
and utilises the firmly defined network variables of the LONMARK<br />
“Pump Controller Object for HVAC Applications” functional profiles.<br />
Operating-data management by BA<br />
Data management by BA systems allows the logging and recording of<br />
cyclical and eventful data. For example:<br />
• Maximum output data for p and Q<br />
• Minimum output data for p and Q<br />
• Current power consumption P 1<br />
• Operating hours<br />
• Cumulative power consumption<br />
• Status reports<br />
• Fault reports with date, time and cause<br />
The multitude of the information and functions listed allows specific<br />
energy and maintenance management and thus contributes to<br />
reducing costs.<br />
It is thus feasible, by relating the performance and work data to the<br />
measured heating load, to assess overall plant efficiencies and performance<br />
data.<br />
204 Subject to change without prior notice 09/2006 WILO AG