Pump Management Systems Wilo-Control<br />

Pump Control<br />

Planning Guide<br />

LON is an open, non-manufacturer-specific system which enables<br />

open, intersectional communication between different components<br />

and systems. It thus offers advantages to planner, installer and operator,<br />

such as:<br />

• Intersectional trade integration<br />

• Non-manufacturer-specific<br />

• Creation of functional added values<br />

• Avoidance of installation and planning errors thanks to a standardised<br />

data interface (prerequisite: no changing transfer media)<br />

• Reduction of installation expenditure in comparison with standalone<br />

systems<br />

• Reduced investment costs through multiple utilisation of sensors<br />

• No expensive gateway solutions are required for data communication<br />

between stand-alone systems<br />

• Flexibility in the event of modifications and retrofitting<br />

• Reduced operating costs thanks to intelligent energy management<br />

• Efficiency and operational reliability due to hydraulic load management<br />

in heating / ventilation / air-conditioning installations<br />

• Overall transparency due to centralised displays, interventions and<br />

monitoring<br />

• Standardised and transparent operation of equipment and buildingservices<br />

systems<br />

• LONWORKS provides for 2 directions of communication:<br />

• Vertical communication between components on the field level and<br />

automation stations on the automation level<br />

• Horizontal communication between components at the field level<br />

It is horizontal communication in particular which allows the set-up<br />

of decentralised structures which operate without higher-level automation<br />

stations. It has thus become possible to realise previously<br />

expensive control tasks with significantly lower installation expenditure;<br />

e.g. a controlled pump with communication capability can<br />

exchange data directly via LON with a valve, a differential-pressure<br />

sensor or a boiler control system and undertake control tasks. In parallel<br />

fashion, the pump can send electrical and hydraulic operating<br />

data for statistical conditioning and if necessary fault and run /<br />

process signals to the higher-level control room and receive higherlevel<br />

commands from this control room.<br />

Communication takes place with the standardised LONTALK protocol<br />

and utilises the firmly defined network variables of the LONMARK<br />

“Pump Controller Object for HVAC Applications” functional profiles.<br />

Operating-data management by BA<br />

Data management by BA systems allows the logging and recording of<br />

cyclical and eventful data. For example:<br />

• Maximum output data for p and Q<br />

• Minimum output data for p and Q<br />

• Current power consumption P 1<br />

• Operating hours<br />

• Cumulative power consumption<br />

• Status reports<br />

• Fault reports with date, time and cause<br />

The multitude of the information and functions listed allows specific<br />

energy and maintenance management and thus contributes to<br />

reducing costs.<br />

It is thus feasible, by relating the performance and work data to the<br />

measured heating load, to assess overall plant efficiencies and performance<br />

data.<br />

204 Subject to change without prior notice 09/2006 WILO AG