10.04.2013 Views

19XR (PIC II) Hermetic Centrifugal Liquid Chillers 50 Hz - Carrier

19XR (PIC II) Hermetic Centrifugal Liquid Chillers 50 Hz - Carrier

19XR (PIC II) Hermetic Centrifugal Liquid Chillers 50 Hz - Carrier

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

4 - BEFORE INITIAL START-UP<br />

4.1 - Necessary checks<br />

4.1.1 - Job Data Required<br />

Checks before system start-up<br />

Before the start-up of the refrigeration system, the complete<br />

installation, including the refrigeration system must be verified<br />

against the installation drawings, dimensional drawings, system<br />

piping and instrumentation diagrams and the wiring diagrams.<br />

During the installation test national regulations must be<br />

followed. If no national regulation exists, paragraph 9-5 of<br />

standard EN 378-2 can be used as a guide.<br />

External visual installation checks:<br />

Compare the complete installation with the refrigeration<br />

system and power circuit diagrams.<br />

Check that all components comply with the design<br />

specifications.<br />

Check that all safety documents and equipments that are<br />

required by current European standards are present.<br />

Verify that all safety and environmental protection<br />

devices and arrangements are in place and comply with<br />

the current European standard.<br />

Verify that all document for pressure containers,<br />

certificates, name plates, files, instruction manuals that are<br />

required documents required by the current European<br />

standards are present.<br />

Verify the free passage of access and safety routes.<br />

Check that ventilation in the plant room is adequate.<br />

Check that refrigerant detectors are present.<br />

Verify the instructions and directives to prevent the<br />

deliberate removal of refrigerant gases that are harmful to<br />

the environment.<br />

Verify the installation of connections.<br />

Verify the supports and fixing elements (materials,<br />

routing and connection).<br />

Verify the quality of welds and other joints.<br />

Check the protection against mechanical damage.<br />

Check the protection against heat.<br />

Check the protection of moving parts.<br />

Verify the accessibility for maintenance or repair and to<br />

check the piping.<br />

Verify the status of the valves.<br />

Verify the quality of the thermal insulation and of the<br />

vapour barriers.<br />

4.1.2 - Equipment Required<br />

mechanic’s tools (refrigeration)<br />

digital volt-ohmmeter (DVM)<br />

clamp-on ammeter<br />

electronic leak detector<br />

absolute pressure manometer or wet-bulb vacuum<br />

indicator<br />

<strong>50</strong>0-V insulation tester (megohmmeter) for compressor<br />

motors with nameplate voltage of 600 V or less, or a <strong>50</strong>00-V<br />

insulation tester for compressor motor rated above 600 V.<br />

4.1.3 - Using the Optional Storage Tank and Pumpout<br />

System<br />

Refer to Pumpout and Refrigerant Transfer Procedures section,<br />

for: pumpout system preparation, refrigerant transfer, and<br />

chiller evacuation.<br />

4.1.4 - Remove Shipping Packaging<br />

Remove any packaging material from the control centre,<br />

control box, guide vane actuator, motor cooling and oil reclaim<br />

solenoids, motor and bearing temperature sensor covers, and<br />

the factory-mounted starter.<br />

4.1.5 - Open Oil Circuit Valves<br />

Check that the oil filter isolation valves (Fig. 4) are open by<br />

removing the valve cap and checking the valve stem.<br />

4.1.6 - Tighten All Gasketed Joints and Guide Vane Shaft<br />

Packing (torque depends on screw diameter)<br />

Gaskets and packing normally relax by the time the chiller<br />

arrives at the jobsite. Tighten all gasketed joints and the guide<br />

vane shaft packing to ensure a leak tight chiller.<br />

4.1.7 - Inspect Water Piping<br />

Refer to piping diagrams provided in the certified drawings, and<br />

the piping instructions in the <strong>19XR</strong> Installation Instructions<br />

manual. Inspect the piping to the cooler and condenser. Be sure<br />

that flow directions are correct and that all piping specifications<br />

have been met.<br />

Do not introduce any significant static or dynamic pressure<br />

into the heat exchange circuit (with regard to the design<br />

operating pressures).<br />

Before any start-up verify that the heat exchange fluid is<br />

compatible with the materials and the water circuit coating.<br />

In case additives or other fluids than those recommended by<br />

<strong>Carrier</strong> s.a are used, ensure that the fluids are not considered as<br />

a gas, and that they belong to class 2, as defined in directive<br />

97/23/EC.<br />

<strong>Carrier</strong> s.a. recommendations on heat exchange fluids:<br />

1. No NH4+ ammonium ions in the water, they are very<br />

detrimental for copper. This is one of the most important<br />

factors for the operating life of copper piping. A content<br />

of several tenths of mg/l will badly corrode the copper<br />

over time.<br />

2. Cl- Chloride ions are detrimental for copper with a risk of<br />

perforations by corrosion by puncture. If possible keep<br />

below 10 mg/l.<br />

2- 3. SO sulphate ions can cause perforating corrosion, if<br />

4<br />

their content is above 30 mg/l.<br />

4. No fluoride ions (2.8 K. Values between 10 and 25<br />

can be recommended. This will facilitate scale deposit that<br />

can limit corrosion of copper. TH values that are too high<br />

can cause piping blockage over time. A total alkalimetric<br />

titre (TAC) below 100 is desirable.<br />

39

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!