10.04.2013 Views

19XR (PIC II) Hermetic Centrifugal Liquid Chillers 50 Hz - Carrier

19XR (PIC II) Hermetic Centrifugal Liquid Chillers 50 Hz - Carrier

19XR (PIC II) Hermetic Centrifugal Liquid Chillers 50 Hz - Carrier

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

To pressurize with dry nitrogen<br />

Another method of leak testing is to pressurize with nitrogen<br />

only and to use a soap bubble solution or an ultrasonic leak<br />

detector to determine if leaks are present. This should only be<br />

done if all refrigerant has been evacuated from the vessel.<br />

1. Connect a copper tube from the pressure regulator on the<br />

cylinder to the refrigerant charging valve.<br />

2. Never apply full cylinder pressure to the pressurizing line.<br />

Follow the listed sequence.<br />

3. Open the charging valve fully.<br />

4. Slowly open the cylinder regulating valve.<br />

5. Observe the pressure gauge on the chiller and close the<br />

regulating valve when the pressure reaches test level. Do<br />

not exceed 965 kPa.<br />

6. Close the charging valve on the chiller. Remove the<br />

copper tube if no longer required.<br />

Repair the leak, retest and apply standing vacuum test<br />

After pressurizing the chiller, test for leaks with an electronic<br />

leak detector, soap bubble solution, or an ultrasonic leak<br />

detector. Bring the chiller back to atmospheric pressure, repair<br />

any leaks found, and retest.<br />

After retesting and finding no leaks, apply a standing vacuum<br />

test, and then dehydrate the chiller. Refer to the Standing<br />

Vacuum Test and Chiller Dehydration in the Before Initial<br />

Start-Up section.<br />

7.1.7 - Checking Guide Vane Linkage<br />

When the chiller is off, the guide vanes are closed and the<br />

actuator mechanism is in the position shown in Fig. 29. If slack<br />

develops in the drive chain, backlash can be eliminated as<br />

follows:<br />

1. With the chiller shut down and the actuator fully closed,<br />

remove the chain guard and loosen the actuator bracket<br />

holddown bolts.<br />

2. Loosen guide vane sprocket adjusting bolts.<br />

3. Pry bracket upwards to remove slack, then retighten the<br />

bracket holddown bolts.<br />

4. Retighten the guide vane sprocket adjusting bolts. Make<br />

sure that the guide vane shaft is rotated fully in the<br />

clockwise direction in order for it to be fully closed.<br />

7.1.8 - Trim Refrigerant Charge<br />

If, to obtain optimal chiller performance, it becomes necessary<br />

to adjust the refrigerant charge, operate the chiller at design load<br />

and then add or remove refrigerant slowly until the difference<br />

between leaving chilled water temperature and the cooler refrigerant<br />

temperature reaches design conditions or becomes a<br />

minimum. Do not overcharge.<br />

Refrigerant may be added either through the storage tank or<br />

directly into the chiller as described in the Charge Refrigerant<br />

into Chiller section.<br />

To remove any excess refrigerant, follow the procedure in<br />

Transfer Refrigerant from Chiller to Pumpout Storage Tank<br />

section, Steps 1a and b.<br />

1. Actuator sprocket<br />

2. Chain guard<br />

3. Guide vane shaft<br />

4. Electronic vane actuator<br />

5. Drive chain<br />

6. Actuator bracket hold-down bolts<br />

7. Guide vane sprocket<br />

8. Guide vane sprocket adjusting bolts<br />

Fig. 29 - Guide vane actuator linkage<br />

7.2 - Weekly maintenance<br />

Check the Lubrication System<br />

Mark the oil level on the reservoir sight glass, and observe the<br />

level each week while the chiller is shut down.<br />

If the level goes below the lower sight glass, check the oil reclaim<br />

system for proper operation. If additional oil is required, add it<br />

through the oil drain charging valve (Fig. 4). A pump is required<br />

for adding oil against refrigerant pressure. The oil charge is<br />

approximately:<br />

Compressor size Oil charge (l)<br />

2 19<br />

3 30<br />

4 38<br />

5 68<br />

The added oil must meet <strong>Carrier</strong> specifications for the <strong>19XR</strong>.<br />

Refer to Changing Oil Filter and Oil Changes section on this<br />

and the next page. Any additional oil that is added should be<br />

logged by noting the amount and date. Any oil that is added<br />

due to oil loss that is not related to service will eventually<br />

return to the sump. It must be removed when the level is high.<br />

51

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!