10.04.2013 Views

19XR (PIC II) Hermetic Centrifugal Liquid Chillers 50 Hz - Carrier

19XR (PIC II) Hermetic Centrifugal Liquid Chillers 50 Hz - Carrier

19XR (PIC II) Hermetic Centrifugal Liquid Chillers 50 Hz - Carrier

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

8. Dissolved oxygen: Any sudden change in water oxygenation<br />

conditions must be avoided. It is as detrimental to<br />

deoxygenate the water by mixing it with inert gas as it is<br />

to over-oxygenate it by mixing it with pure oxygen. The<br />

disturbance of the oxygenation conditions encourages<br />

destabilisation of copper hydroxides and enlargement of<br />

particles.<br />

9. Specific resistance – electric conductivity: the higher the<br />

specific resistance, the slower the corrosion tendency.<br />

Values above 3000 Ohm/cm are desirable. A neutral<br />

environment favours maximum specific resistance values.<br />

For electric conductivity values in the order of 200-6000<br />

S/cm can be recommended.<br />

10. pH: Ideal case pH neutral at 20-25°C<br />

7 < pH < 8<br />

If the water circuit must be emptied for longer than one month,<br />

the complete circuit must be placed under nitrogen charge to<br />

avoid any risk of corrosion by differential aeration.<br />

Charging and removing heat exchange fluids should be done<br />

with devices that must be included on the water circuit by the<br />

installer. Never use the unit heat exchangers to add heat<br />

exchange fluid.<br />

Piping systems must be properly vented, with no stress on<br />

waterbox nozzles and covers. Use flexible connections to<br />

reduce the transmission of vibrations. Water flows through the<br />

cooler and condenser must meet job requirements. Measure the<br />

pressure drop across cooler and across condenser and compare<br />

this with the nominal values (see selection document).<br />

If the optional pumpout storage tank and/or pumpout system<br />

are installed, check to ensure the pumpout condenser water has<br />

been piped in. Check for field-supplied shutoff valves and<br />

controls as specified in the job data. Check for refrigerant leaks<br />

on field-installed piping. See Fig. 19 and 20.<br />

4.1.8 Check Relief Devices<br />

Be sure that relief devices have been piped to the outdoors in<br />

compliance with standard EN 378-2. Piping connections must<br />

allow for access to the valve mechanism for periodic inspection<br />

and leak testing. <strong>19XR</strong> relief valves are set to relieve at 1275 kPa<br />

chiller heat exchanger design pressure.<br />

4.2 - Chiller Tightness<br />

4.2.1 - Check chiller tightness<br />

Figure 25 outlines the proper sequence and procedures for leak<br />

testing.<br />

<strong>19XR</strong> chillers are shipped with the refrigerant contained in the<br />

condenser shell and the oil charge shipped in the compressor.<br />

The cooler will have a 225 kPa refrigerant charge. Units may<br />

be ordered with the refrigerant shipped separately, along with a<br />

225 kPa nitrogen-holding charge in each vessel. To determine if<br />

there are any leaks, the chiller should be charged with refrigerant.<br />

Use an electronic leak detector to check all flanges and solder<br />

joints after the chiller is pressurized. If any leaks are detected,<br />

follow the leak test procedure.<br />

40<br />

If the chiller is spring isolated, keep all springs blocked in both<br />

directions in order to prevent possible piping stress and damage<br />

during the transfer of refrigerant from vessel to vessel during the<br />

leak test process, or any time refrigerant is transferred. Adjust<br />

the springs when the refrigerant is in operating condition, and<br />

when the water circuits are full.<br />

4.2.2 - Refrigerant Tracer<br />

<strong>Carrier</strong> recommends the use of an environmentally acceptable<br />

refrigerant tracer for leak testing with an electronic detector.<br />

Ultrasonic leak detectors also can be used if the chiller is under<br />

pressure.<br />

WARNING: Do not use air or oxygen as a means of pressurizing<br />

the chiller. Mixtures of HFC-134a and air can undergo<br />

combustion.<br />

4.2.3 - Leak Test Chiller<br />

Due to regulations regarding refrigerant emissions and the difficulties<br />

associated with separating contaminants from refrigerant,<br />

<strong>Carrier</strong> recommends the following leak test procedures. See<br />

Fig. 25 for an outline of the leak test procedures.<br />

1. If the pressure readings are normal for chiller condition:<br />

a. Evacuate the holding charge from the vessels, if<br />

present.<br />

b. Raise the chiller pressure, if necessary, by adding<br />

refrigerant until pressure is at equivalent saturated<br />

pressure for the surrounding temperature. Follow the<br />

pumpout procedures in the Transfer Refrigerant from<br />

Pumpout Storage Tank to Chiller section, Steps 1a - e.<br />

WARNING: Never charge liquid refrigerant into the<br />

chiller if the pressure in the chiller is less than 241 kPa<br />

for HFC-134a. Charge as a gas only, with the cooler and<br />

condenser pumps running, until this pressure is reached,<br />

using PUMP-DOWN LOCKOUT and TERMINATE<br />

LOCKOUT mode on the <strong>PIC</strong> <strong>II</strong>. Flashing of liquid<br />

refrigerant at low pressures can cause tube freeze-up<br />

and considerable damage.<br />

c. Leak test chiller as outlined in Steps 3 -9.<br />

2. If the pressure readings are abnormal for chiller<br />

condition:<br />

a. Prepare to leak test chillers shipped with refrigerant<br />

(Step 2h).<br />

b. Check for large leaks by connecting a nitrogen bottle<br />

and raising the pressure to 207 kPa. Soap test all joints.<br />

If the test pressure holds for 30 minutes, prepare the<br />

test for small leaks (Steps 2g - h).<br />

c. Plainly mark any leaks which are found.<br />

d. Release the pressure in the system.<br />

e. Repair all leaks.<br />

f. Retest the joints that were repaired.<br />

g. After successfully completing the test for large leaks,<br />

remove as much nitrogen, air, and moisture as possible,<br />

given the fact that small leaks may be present in the<br />

system. This can be accomplished by following the<br />

dehydration procedure, outlined in the Chiller Dehydration<br />

section below.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!