<strong>Levelflex</strong> M <strong>FMP40</strong> with HART/4...20 mA Mounting<br />

Other installations<br />

• Select the mounting location such that the<br />

distance to internals (5) (e.g. limit switch,<br />

struts) > is 300 mm over the entire length of<br />

the probe, also during operation.<br />

• Probe must within the measuring span not<br />

touch any internals during operation. If<br />

necessary: when using rope probes the probe<br />

end (4) may be fixed to ensure that → ä 29!<br />

Optimization options<br />

• Interference echo suppression: Measurement<br />

can be optimised by electronically tuning out<br />

interference echoes.<br />

Minimum distance B of the probe to the container wall:<br />

Wall min. distance B<br />

Metal 100 mm for smooth walls<br />

Plastic 100 mm, min. 300 mm to metallic components outside of the tank<br />

Concrete 0.5 m/20", otherwise the max. possible measuring range is reduced<br />

Distance to protruding internals min. 300 mm.<br />