<strong>Levelflex</strong> M <strong>FMP40</strong> with HART/4...20 mA Wiring<br />

4.3 Recommended connection<br />

4.3.1 Equipotential bonding<br />

Connect the Equipotential bonding to the external ground terminal (1) of the transmitter.<br />

1<br />

F12/F23 housing T12 housing<br />

L00-FMP4xxxx-17-00-00-en-032<br />

4.3.2 Wiring screened cable<br />

" Caution!<br />

In Ex applications, the instrument must only be grounded on the sensor side. Further safety<br />

instructions are given in the separate documentation for applications in explosion hazardous areas.<br />

4.4 Degree of protection<br />

• with closed housing tested according to<br />

– IP68, NEMA6P (24 h at 1.83 m under water surface)<br />

– IP66, NEMA4X<br />

• with open housing: IP20, NEMA1 (also ingress protection of the display)<br />

4.5 Post-connection check<br />

After wiring the measuring instrument, perform the following checks:<br />

• Is the terminal allocation correct (see → ä 36 and → ä 37)?<br />

• Is the cable gland tight?<br />

• Is the housing cover screwed tight?<br />

• If auxiliary power is available:<br />

Is the instrument ready for operation and is the liquid crystal display visible?<br />

Endress + Hauser 41<br />

1