Levelflex M FMP40 - Process Centre Of Excellence.
Levelflex M FMP40 - Process Centre Of Excellence.
Levelflex M FMP40 - Process Centre Of Excellence.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Levelflex</strong> M <strong>FMP40</strong> with HART/4...20 mA Commissioning<br />
Evaluation of the measurement:<br />
• The map must correspond to the course of the envelope curve (for rod probes up to approx. 5 cm<br />
and for rope probes up to approx. 25 cm before the end of the probe) when the tank is empty.<br />
• Amplitudes in the differential curve should be at a level of 0 mV when the tank is empty and lie<br />
within the span that is specified by the probe-specific blocking distances. In order to not detect<br />
any interference echoes, there must be no signals that exceed the echo threshold when the tank<br />
is empty.<br />
• For partially-filled tanks, the map may only differ from the envelope curve at the position of the<br />
level echo. The level signal is then detected unequivocally as a positive signal in the differential<br />
curve. For detecting the level echo, the amplitude must lie above the echo threshold.<br />
[mV]<br />
400.00<br />
300.00<br />
200.00<br />
100.00<br />
0.00<br />
-100.00<br />
-200.00<br />
-300.00<br />
-400.00<br />
-500.00<br />
0.00<br />
Launch pulse<br />
F<br />
0.20<br />
0.40<br />
Negative<br />
probe end signal<br />
0.60<br />
[mV]<br />
400.00<br />
300.00<br />
200.00<br />
100.00<br />
0.00<br />
-100.00<br />
-200.00<br />
-300.00<br />
-400.00<br />
-500.00<br />
0.00<br />
6.8.3 User-specific applications (operation)<br />
0.80<br />
Envelope curve<br />
L00-<strong>FMP40</strong>xxx-05-00-00-en-025<br />
For details of setting the parameters of user-specific applications, see separate documentation<br />
BA245F/00/en - description of the instrument functions of the <strong>Levelflex</strong> M.<br />
Endress + Hauser 73<br />
E<br />
F<br />
(1.00 m, -143.00 mV)<br />
0.20<br />
LN<br />
1.00<br />
[m]<br />
0.40<br />
0.60<br />
[mV]<br />
400.00<br />
300.00<br />
200.00<br />
100.00<br />
0.00<br />
-100.00<br />
-200.00<br />
-300.00<br />
-400.00<br />
-500.00<br />
0.00<br />
0.80<br />
F<br />
0.20<br />
E<br />
(0.98 m, 0.00 mV)<br />
Differential curve = Envelope curve Mapping<br />
LN<br />
1.00<br />
0.40<br />
[m]<br />
0.60<br />
Mapping<br />
0.80<br />
E<br />
(0.99 m, -137.94 mV)<br />
LN<br />
1.00<br />
[m]