Maintenance <strong>Levelflex</strong> M <strong>FMP40</strong> with HART/4...20 mA<br />

7 Maintenance<br />

The <strong>Levelflex</strong> M measuring instrument requires no special maintenance.<br />

Exterior cleaning<br />

When cleaning the <strong>Levelflex</strong> M , always use cleaning agents that do not attack the surface of the<br />

housing and the seals.<br />

Repairs<br />

The Endress+Hauser repair concept assumes that the measuring devices have a modular design and<br />

that customers are able to undertake repairs themselves. Spare parts are contained in suitable kits.<br />

They contain the related replacement instructions. All the spare parts kits which you can order from<br />

Endress+Hauser for repairs to the <strong>Levelflex</strong> M are listed with their order numbers on → ä 86 and<br />

89. Please contact Endress+Hauser Service for further information on service and spare parts.<br />

Repairs to Ex-approved devices<br />

When carrying out repairs to Ex-approved devices, please note the following:<br />

• Repairs to Ex-approved devices may only be carried out by trained personnel or by<br />

Endress+Hauser Service.<br />

• Comply with the prevailing standards, national Ex-area regulations, safety instructions (XA) and<br />

certificates.<br />

• Only use original spare parts from Endress+Hauser.<br />

• When ordering a spare part, please note the device designation on the nameplate. Only replace<br />

parts with identical parts.<br />

• Carry out repairs according to the instructions. On completion of repairs, carry our the specified<br />

routine test on the device.<br />

• Only Endress+Hauser Service may convert a certified device into a different certified variant.<br />

• Document all repair work and conversions.<br />

Replacement<br />

After a complete <strong>Levelflex</strong> M or electronic module has been replaced, the parameters can be<br />

downloaded into the instrument again via the communication interface. Prerequisite to this is that<br />

the data were uploaded to the PC beforehand using the ToF Tool.<br />

Measurement can continue without having to carry out a new setup.<br />

• You may have to activate linearisation (see BA245F – "Description of the instrument functions"<br />

on the enclosed CD-ROM.)<br />

• You may need to record the tank map again (see Basic Setup)<br />

After an probe or electronic has been replaced, a new calibration must be carried out. This is<br />

described in the repair instructions.<br />

74 Endress + Hauser