Trouble-shooting <strong>Levelflex</strong> M <strong>FMP40</strong> with HART/4...20 mA<br />
9.3 Application errors<br />
Error Output Possible cause Remedy<br />
A warning or alarm<br />
has occurred.<br />
Measured value<br />
(00) is incorrect<br />
No change off<br />
measured value on<br />
filling/emptying<br />
E 641 (loss of<br />
echo) after turn on<br />
the power supply<br />
Depending on the configuration See table of<br />
error messages<br />
(→ ä 82)<br />
D m/ft (008)<br />
F m/ft<br />
E m/ft<br />
20 mA/100%<br />
expected<br />
actual<br />
4 mA/0% t →<br />
20 mA/100%<br />
expected<br />
L00-FMP4xxxx-19-00-00-en-019<br />
actual<br />
4 mA/0% t →<br />
L00-FMR2xxxx-19-00-00-en-014<br />
If the instrument is configured to Hold by loss of<br />
echo the output is set to any value/current.<br />
Measured distance<br />
(008) OK?<br />
1. See table of error messages<br />
(→ ä 82)<br />
yes → 1. Check empty calibr. (005) and<br />
full calibr. (006)<br />
2. Check linearisation:<br />
→ level/ullage (040)<br />
→ max. scale (046)<br />
→ diameter vessel (047)<br />
→ Check table<br />
84 Endress + Hauser<br />
no ↓<br />
An interference echo<br />
may have been<br />
evaluated.<br />
Interference echo from<br />
installations, nozzle<br />
or extension on the<br />
probe<br />
noise level during the<br />
initialisation phase to<br />
high.<br />
yes → 1. Carry out tank mapping<br />
→ basic setup<br />
1. Carry out tank mapping<br />
→ basic setup<br />
2. If necessary, clean probe<br />
3. If necessary, select better<br />
mounting position<br />
Repeat once more empty calibr.<br />
(005).<br />
Caution!<br />
Before conformation change with O<br />
or S to the edit mode.