10 Technical data<br />
10.1 Additional technical data<br />
10.1.1 Input<br />
Measured variable The measured variable is the distance between a reference point (see Fig. on → ä 16) and the<br />
product surface.<br />
Subject to the input empty distance (E, see Fig. on → ä 104), the level is calculated.<br />
Alternatively, the level can be converted by means of linearisation (32 points) into other variables<br />
(volume, mass).<br />
10.1.2 Output<br />
Output signal 4…20 mA with HART protocol<br />
Signal on alarm Error information can be accessed via the following interfaces:<br />
•Local display:<br />
– Error symbol (→ ä 45)<br />
– Plain text display<br />
• Current output, signal on error can be selected (e.g. according to NAMUR recommendation NE<br />
43).<br />
• Digital interface<br />
Linearization The <strong>Levelflex</strong> M linearisation function enables conversion of the measured value into any desired<br />
length or volume units and mass or %. Linearisation tables for volume calculation in cylindrical tanks<br />
are pre-programmed. Any other tables from up to 32 value pairs can be input manually or semiautomatically.<br />
The creation of a linearisation table with the ToF Tool or FieldCare is particularly convenient.<br />
Reference operating<br />
conditions<br />
10.1.3 Performance characteristics<br />
• temperature = +20 °C (68 °F) ±5 °C (9 °F)<br />
• pressure = 1013 mbar abs. (14.7 psia) ±20 mbar (0.3 psi)<br />
• humidity = 65 % ±20%<br />
• Reflection factor ≥ 0.8 (surface of the water for coax probe, metal plate for rod and rope probe<br />
with min. 1 m ∅)<br />
• Flange for rod or rope probe ≥ 30 cm ∅<br />
• Distance to obstructions ≥ 1m<br />
Maximum measured error Is in Function group "basic setup" (00) starting from → ä 55.<br />
Resolution • Digital: 1 mm<br />
• analog: 0.03 % of the measuring range<br />
Reaction time The reaction time is dependent on the configuration.<br />
Shortest time:<br />
• 2-wire electronics: 1 s<br />
• 4-wire electronics: 0.7 s<br />
94 Endress + Hauser