Levelflex M FMP40 - Process Centre Of Excellence.
Levelflex M FMP40 - Process Centre Of Excellence.
Levelflex M FMP40 - Process Centre Of Excellence.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Wiring <strong>Levelflex</strong> M <strong>FMP40</strong> with HART/4...20 mA<br />
4.2 Connecting the measuring unit<br />
Terminal compartment<br />
Three housings are available:<br />
• Aluminium housing F12 with additionally sealed terminal compartment for:<br />
–standard,<br />
– EEx ia.<br />
• Aluminium housing T12 with separate terminal compartment for:<br />
–standard,<br />
– EEx e,<br />
– EEx d<br />
– EEX ia (with overvoltage protection).<br />
• Stainless steel 316L housing F23 for:<br />
–standard,<br />
– EEx ia.<br />
After mounting, the housing can be turned 350° in order to simplify access to the display and the<br />
terminal compartment.<br />
F12 housing T12 housing<br />
F23 housing<br />
sealed terminal<br />
compartment<br />
1 2 3 4<br />
1 2 3 4 1 2 3 4<br />
L00-FMR2xxxx-04-00-00-en-019<br />
The instrument data are given on the nameplate together with important information regarding the<br />
analog output and voltage supply. Housing orientation regarding the wiring see "Turn housing" on<br />
→ ä 35.<br />
Load HART<br />
Minimum load for Hart communication: 250 Ω<br />
Ground connection<br />
It is necessary to make a good ground connection to the ground terminal on the outside of the<br />
housing, in order to achieve EMC security.<br />
Cable gland<br />
Terminals<br />
for wire cross-sections of 0.5...2.5 mm2 Type Clamping area<br />
Standard, EEx ia, IS Plastic M20x1.5 5...10 mm<br />
EEx em, EEx nA Metal M20x1.5 7...10.5 mm<br />
38 Endress + Hauser