Wiring <strong>Levelflex</strong> M <strong>FMP40</strong> with HART/4...20 mA<br />

4.2 Connecting the measuring unit<br />

Terminal compartment<br />

Three housings are available:<br />

• Aluminium housing F12 with additionally sealed terminal compartment for:<br />

–standard,<br />

– EEx ia.<br />

• Aluminium housing T12 with separate terminal compartment for:<br />

–standard,<br />

– EEx e,<br />

– EEx d<br />

– EEX ia (with overvoltage protection).<br />

• Stainless steel 316L housing F23 for:<br />

–standard,<br />

– EEx ia.<br />

After mounting, the housing can be turned 350° in order to simplify access to the display and the<br />

terminal compartment.<br />

F12 housing T12 housing<br />

F23 housing<br />

sealed terminal<br />

compartment<br />

1 2 3 4<br />

1 2 3 4 1 2 3 4<br />

L00-FMR2xxxx-04-00-00-en-019<br />

The instrument data are given on the nameplate together with important information regarding the<br />

analog output and voltage supply. Housing orientation regarding the wiring see "Turn housing" on<br />

→ ä 35.<br />

Load HART<br />

Minimum load for Hart communication: 250 Ω<br />

Ground connection<br />

It is necessary to make a good ground connection to the ground terminal on the outside of the<br />

housing, in order to achieve EMC security.<br />

Cable gland<br />

Terminals<br />

for wire cross-sections of 0.5...2.5 mm2 Type Clamping area<br />

Standard, EEx ia, IS Plastic M20x1.5 5...10 mm<br />

EEx em, EEx nA Metal M20x1.5 7...10.5 mm<br />

38 Endress + Hauser