<strong>Levelflex</strong> M <strong>FMP40</strong> with HART/4...20 mA Trouble-shooting<br />

Device displays a<br />

level when the<br />

tank is empty.<br />

Measured value<br />

incorrect (slope<br />

error in the entire<br />

measuring range)<br />

20 mA/100%<br />

actual<br />

expected<br />

4 mA/0% t →<br />

20 mA/100%<br />

L00-FMP4xxxx-19-00-00-en-020<br />

expected<br />

2.) actual<br />

1.) actual<br />

4 mA/0% t →<br />

L00-FMP4xxxx-19-00-00-en-021<br />

Incorrect probe length 1. Carry out automatic probe length<br />

detection when the tank is<br />

empty.<br />

2. Carry out mapping over entire<br />

probe when the tank is empty<br />

(probe free!).<br />

Tank properties<br />

incorrect.<br />

Medium properties<br />

incorrect.<br />

LN < 4 m and "Aluminium tank" tank<br />

properties selected<br />

→ Calibration not possible.<br />

→ Selection<br />

→ Select standard<br />

→ Thresholds too high<br />

Select lower medium properties.<br />