<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
5.5 Boiler<br />
Difference 11046<br />
Circuit Setting range Factory setting<br />
1 (OFF /) 1 ... 50 K 8 K<br />
The burner is switched ON and OFF to maintain the desired boiler<br />
temperature. Set the difference between the cut-in and cut-out temperature.<br />
OFF: (Only in <strong>A275</strong> applications):<br />
The boiler temperature difference is set<br />
automatically according to the momentary load of<br />
the boiler and the temperature conditions in the<br />
heating system.<br />
1 ... 50 K: The boiler temperature difference is set to a<br />
fixed value according to the boiler manufacturer<br />
specification.<br />
Max. T limit 11049<br />
Circuit Setting range Factory setting<br />
1 40 ... 150 °C 90 °C<br />
<strong>A275</strong> applications:<br />
If the boiler / flow temperature exceeds the set value, the burner is cut-out.<br />
<strong>A375</strong> applications:<br />
If the boiler / flow temperature exceeds the set value, burner steps are<br />
cut-out in intervals of 5 sec.<br />
40 ... 150: Set the limitation temperature.<br />
Min. ON time 11071<br />
Circuit Setting range Factory setting<br />
1 0 ... 9 m 0 m<br />
Set the minimum operation time (minutes) for the burner.<br />
1 ... 9 m: The boiler can be protected against condensation /<br />
corrosion caused by insufficient heat-up time at each<br />
burner start. The protection is obtained by a minimum<br />
operation time of the burner. With this setting the boiler<br />
temperature difference (ID no. 11046 ‘Difference’) is<br />
overruled.<br />
Temp.<br />
ON OFF<br />
Actual boiler / flow<br />
temp.<br />
Difference<br />
Desired boiler / flow<br />
temp.<br />
Time<br />
The boiler temperature difference is symmetrical around the desired<br />
boiler temperature, i.e. half the value is above and half the value is<br />
below this temperature.<br />
'Max. T limit' overrules 'Min. ON time'.<br />
'Min. ON time' is overruled by 'Max. T limit'.<br />
114 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy