<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

5.5 Boiler<br />

Difference 11046<br />

Circuit Setting range Factory setting<br />

1 (OFF /) 1 ... 50 K 8 K<br />

The burner is switched ON and OFF to maintain the desired boiler<br />

temperature. Set the difference between the cut-in and cut-out temperature.<br />

OFF: (Only in <strong>A275</strong> applications):<br />

The boiler temperature difference is set<br />

automatically according to the momentary load of<br />

the boiler and the temperature conditions in the<br />

heating system.<br />

1 ... 50 K: The boiler temperature difference is set to a<br />

fixed value according to the boiler manufacturer<br />

specification.<br />

Max. T limit 11049<br />

Circuit Setting range Factory setting<br />

1 40 ... 150 °C 90 °C<br />

<strong>A275</strong> applications:<br />

If the boiler / flow temperature exceeds the set value, the burner is cut-out.<br />

<strong>A375</strong> applications:<br />

If the boiler / flow temperature exceeds the set value, burner steps are<br />

cut-out in intervals of 5 sec.<br />

40 ... 150: Set the limitation temperature.<br />

Min. ON time 11071<br />

Circuit Setting range Factory setting<br />

1 0 ... 9 m 0 m<br />

Set the minimum operation time (minutes) for the burner.<br />

1 ... 9 m: The boiler can be protected against condensation /<br />

corrosion caused by insufficient heat-up time at each<br />

burner start. The protection is obtained by a minimum<br />

operation time of the burner. With this setting the boiler<br />

temperature difference (ID no. 11046 ‘Difference’) is<br />

overruled.<br />

Temp.<br />

ON OFF<br />

Actual boiler / flow<br />

temp.<br />

Difference<br />

Desired boiler / flow<br />

temp.<br />

Time<br />

The boiler temperature difference is symmetrical around the desired<br />

boiler temperature, i.e. half the value is above and half the value is<br />

below this temperature.<br />

'Max. T limit' overrules 'Min. ON time'.<br />

'Min. ON time' is overruled by 'Max. T limit'.<br />

114 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy