<strong>A275</strong>.2, example d<br />
Boiler ON / OFF control for a heating and a DHW circuit. DHW priority. The boiler circuit is equipped with a low loss header.<br />
* = pressure relief valve<br />
S1<br />
B1<br />
S3<br />
S5<br />
P1<br />
P3/M1<br />
<strong>ECL</strong> <strong>210</strong> / (<strong>310</strong>)<br />
The pump in the boiler circuit is not controlled.<br />
At DHW heating P3 (changeover valve) is activated and the desired boiler temperature lies a number of degrees above the desired DHW<br />
temperature.<br />
P1 is switched ON.<br />
Special settings for type <strong>A275</strong>.2, example d:<br />
Navigation: ID no.: Recommended setting:<br />
DHW circuit (circuit 2)<br />
DHW heating is managed by changeover valve P3 / M1:<br />
MENU \ Settings \ Application: 'Ch.-o. valve / P' 12051 OFF<br />
The desired DHW heating temperature must influence the desired boiler temperature:<br />
MENU \ Settings \ Application: ‘Tank, sec./prim.' 12053 OFF<br />
24 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy<br />