<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

<strong>A275</strong>.2, example d<br />

Boiler ON / OFF control for a heating and a DHW circuit. DHW priority. The boiler circuit is equipped with a low loss header.<br />

* = pressure relief valve<br />

S1<br />

B1<br />

S3<br />

S5<br />

P1<br />

P3/M1<br />

<strong>ECL</strong> <strong>210</strong> / (<strong>310</strong>)<br />

The pump in the boiler circuit is not controlled.<br />

At DHW heating P3 (changeover valve) is activated and the desired boiler temperature lies a number of degrees above the desired DHW<br />

temperature.<br />

P1 is switched ON.<br />

Special settings for type <strong>A275</strong>.2, example d:<br />

Navigation: ID no.: Recommended setting:<br />

DHW circuit (circuit 2)<br />

DHW heating is managed by changeover valve P3 / M1:<br />

MENU \ Settings \ Application: 'Ch.-o. valve / P' 12051 OFF<br />

The desired DHW heating temperature must influence the desired boiler temperature:<br />

MENU \ Settings \ Application: ‘Tank, sec./prim.' 12053 OFF<br />

24 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy<br />

*<br />

A1<br />

S6<br />

S7<br />

①<br />

②<br />

<strong>Danfoss</strong><br />

87H2168.10