<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

<strong>A375</strong>.1, example I<br />

Up to 8 x boiler ON / OFF control for a heating circuit. The first two boilers (high efficiency) have highest priority.<br />

S1<br />

* = pressure relief valve<br />

B1 B2 B3<br />

B8<br />

S5<br />

S3<br />

<strong>ECL</strong> <strong>310</strong><br />

+ ECA 32<br />

The first two boilers can be heat pumps<br />

The extension module ECA 32 is used to control boiler 5, 6, 7 and 8.<br />

Sequence for the boilers: Boiler 1, 2, 3 - 4 - 5 - 6 - 7 - 8. Next day: Boiler 1, 2, 4 - 5 - 6 - 7 - 8 - 3. Following day: Boiler 1, 2, 5 - 6 - 7 - 8 - 3<br />

- 4 and so on.<br />

Burner steps are activated according to heat demand.<br />

The last burner step can be disabled if the outdoor temperaure is higher than a set value.<br />

Special settings for type <strong>A375</strong>.1, example i:<br />

Navigation: ID no.: Recommended setting:<br />

Heating circuit (circuit 1)<br />

Sequence type (code) for controlling the burners:<br />

MENU \ Settings \ Boiler: 'Sequence type' 11072 2<br />

Number of total burner steps:<br />

MENU \ Settings \ Boiler: ‘Steps' 11073 1 .... 8<br />

40 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy<br />

P1<br />

A1<br />

*<br />

S7<br />

①<br />

<strong>Danfoss</strong><br />

87H2187.10