<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

5.6 Application<br />

ECA addr. (choice of Remote Control Unit) 11010<br />

Circuit Setting range Factory setting<br />

1 OFF / A / B OFF<br />

Decides the communication with the Remote Control Unit.<br />

OFF: No Remote Control Unit. Only room temperature sensor,<br />

if any.<br />

A: Remote Control Unit ECA 30 / 31 with address A.<br />

B: Remote Control Unit ECA 30 / 31 with address B.<br />

Demand offset 11017<br />

Circuit Setting range Factory setting<br />

1 OFF / 1 ... 20 K OFF<br />

The desired flow temperature in heating circuit 1 can be influenced by the<br />

demand for a desired flow temperature from another controller (slave) or<br />

another circuit.<br />

OFF: The desired flow temperature in circuit 1 is not<br />

influenced by the demand of any other controller (slave<br />

or circuit 2).<br />

1 ... 20: The desired flow temperature is increased by the set<br />

value in ‘Demand offset’, if the demand of the slave /<br />

circuit 2 is higher.<br />

P demand 11050<br />

Circuit Setting range Factory setting<br />

1 OFF / ON OFF<br />

Choose conditions for the circulation pump in the heating circuit.<br />

OFF: The circulation pump is ON when the desired flow<br />

temperature in the heating circuit is higher than the<br />

value set in 'P heat T'.<br />

ON: The circulation pump is ON when the desired flow<br />

temperature from slaves is higher than the value set in<br />

'P heat T'.<br />

Send desired T 11500<br />

Circuit Setting range Factory setting<br />

1 OFF / ON OFF<br />

When the controller acts as a slave controller in a master / slave system,<br />

information about the desired flow temperature can be sent to the master<br />

controller via the <strong>ECL</strong> 485 bus.<br />

OFF: Information about the desired flow temperature is not<br />

sent to the master controller.<br />

ON: Information about the desired flow temperature is sent<br />

to the master controller.<br />

The Remote Control Unit has no influence on the DHW control.<br />

The Remote Control Unit must be set accordingly (A or B).<br />

Temp. Setting in<br />

‘Demand offset’<br />

Des. flow temp.,<br />

circuit 1<br />

Des. flow temp.,<br />

circuit 2<br />

Time<br />

The function of ‘Demand offset’ can compensate for heat losses<br />

between master and slave controlled systems.<br />

The circulation pump is always controlled according to frost protection<br />

conditions.<br />

In the master controller, 'Demand offset' must be set to a value in order<br />

to react on a desired flow temperature from a slave controller.<br />

When the controller acts as a slave, its address must be 1, 2, 3 ... 9 in<br />

order to send the desired temperature to the master (see the section<br />

‘Miscellaneous’, ‘Several controllers in the same system’).<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 119