<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

DHW priority (closed valve / normal operation) 12052<br />

Circuit Setting range Factory setting<br />

2 OFF / ON OFF<br />

The heating circuit can be closed when the controller acts as slave and when<br />

DHW heating / charging is active in the master.<br />

OFF: The flow temperature control remains unchanged<br />

during active DHW heating / charging in the master<br />

controller.<br />

ON: The valve in the heating circuit is closed* during active<br />

DHW heating / charging in the master controller.<br />

* The desired flow temperature is set to the value set in<br />

‘Frost pr. T’<br />

P frost T 12077<br />

Circuit Setting range Factory setting<br />

2 OFF / -10 ... 20 °C 2 °C<br />

When the outdoor temperature is below the set temperature in ‘P frost T’,<br />

the controller automatically switches ON the circulation pump to protect<br />

the system.<br />

OFF: No frost protection.<br />

-10 ... 20: The circulation pump is ON when the outdoor<br />

temperature is below the set value.<br />

P heat T (heat demand) 12078<br />

Circuit Setting range Factory setting<br />

2 5 ... 40 °C 20 °C<br />

When the desired flow temperature is above the set temperature in ‘P heat T’,<br />

the controller automatically switches ON the circulation pump.<br />

5 ... 40: The circulation pump is switched ON when the desired<br />

flow temperature is above the set value.<br />

P post-run 12040<br />

Circuit Setting range Factory setting<br />

2 0 ... 99 m 3 m<br />

The circulation pump in the heating circuit can be ON for a number of<br />

minutes (m) after heating stop (the desired flow temperature gets lower<br />

than the setting in 'P heat T' (ID no. 12078)).<br />

This function can utilize the remaining heat in e.g. a heat exchanger.<br />

0: The circulation pump stops immediately after the<br />

heating stop.<br />

1 ... 99: The circulation pump is ON for the set time after the<br />

heating stop.<br />

This setting must be considered if this controller is a slave.<br />

Under normal conditions, your system is not frost protected if your<br />

setting is below 0 °C or OFF.<br />

For water-based systems, a setting of 2 °C is recommended.<br />

The valve is fully closed as long as the pump is not switched on.<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 141