6.2 Tank temperature<br />

Charge difference 12193<br />

Circuit Setting range Factory setting<br />

2 1 ... 50 K 15 K<br />

Number of degrees above the desired DHW temperature that will result in<br />

the desired boiler temperature for DHW heating.<br />

1... 50: Number of degrees to be added to the desired DHW<br />

temperature to obtain the desired boiler temperature<br />

for DHW heating.<br />

Start difference 12195<br />

Circuit Setting range Factory setting<br />

2 –50 ... –1 K –3 K<br />

Set the number of degrees below the desired DHW temperature that will<br />

start the DHW heating (charging).<br />

-50 ... –1: Set the number of degrees.<br />

Temp.<br />

° C<br />

DHW heating<br />

Charge difference<br />

Stop difference<br />

Des. DHW temp.<br />

Start difference<br />

Actual DHW temp.<br />

Time<br />

The desired DHW temperature is related to the tank temperature<br />

sensor.<br />

Example:<br />

Desired DHW temp.: 55 °C<br />

Start difference: -3 K<br />

Result:<br />

The DHW heating starts when the temperature measured by the tank<br />

temperature sensor (upper) is lower than 52 °C.<br />

Temp.<br />

° C<br />

DHW heating<br />

Start difference<br />

Desired DHW temp.<br />

DHW temp.<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 125<br />