<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

6.4 Return limit<br />

The return temperature limitation can be based on the outdoor<br />

temperature. The relationship between the return temperature<br />

limits and outdoor temperature is set in two coordinates.<br />

The outdoor temperature coordinates are set in 'High T out X1'<br />

and 'Low T out X2'. The return temperature coordinates are set in<br />

'High limit Y2' and 'Low limit Y1'.<br />

The controller automatically changes the desired boiler / flow<br />

temperature to obtain an acceptable return temperature when the<br />

return temperature falls below or gets higher than the calculated<br />

limit.<br />

This limitation is based on a PI regulation where P ('Infl.' factor)<br />

responds quickly to deviations and I ('Adapt. time') responds slower<br />

and over time removes the small offsets between the desired and<br />

actual values. This is done by changing the desired boiler / flow<br />

temperature.<br />

High T out X1 (return temp. limitation, high limit, X-axis) 12031<br />

Circuit Setting range Factory setting<br />

2 -60 ... 20 °C 15 °C<br />

Set the outdoor temperature for the low return temperature limitation.<br />

The corresponding Y coordinate is set in 'Low limit Y1'.<br />

Low limit Y1 (return temp. limitation, low limit, Y-axis) 12032<br />

Circuit Setting range Factory setting<br />

2 10 ... 150 °C 40 °C<br />

Set the return temperature limitation referring to the outdoor temperature<br />

set in 'High T out X1'.<br />

The corresponding X coordinate is set in 'High T out X1'.<br />

Low T out X2 (return temp. limitation, low limit, X-axis) 12033<br />

Circuit Setting range Factory setting<br />

2 -60 ... 20 °C -15 °C<br />

Set the outdoor temperature for the high return temperature limitation.<br />

The corresponding Y coordinate is set in 'High limit Y2'.<br />

High limit Y2<br />

Low limit Y1<br />

Influence<br />

Return temperature limitation<br />

° C<br />

60<br />

40<br />

-15<br />

15<br />

Low T out X2 High T out X1<br />

° C<br />

‘Infl. - min.’ > 0<br />

‘Limit’<br />

‘Infl. - max.’ > 0<br />

Return temperature<br />

‘Infl. - max.’ < 0<br />

‘Infl. - min.’ < 0<br />

Outdoor temp.<br />

If the ‘Infl.’ factor is too high and / or the ‘Adapt. time’ too low, there is<br />

a risk of unstable control.<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 129