<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

Reaction, o. band (outside band) (<strong>A375</strong> applications) 11074<br />

Circuit Setting range Factory setting<br />

1 5 ... 6000 s 60 s<br />

The set time (in seconds) determines the burner cut-in / cut-out when the<br />

boiler / flow temperature is outside the ‘Band limit’ ID no. 11048.<br />

Two conditions must be met in order to cut-in / cut-out the next burner step:<br />

• the set time has elapsed after the latest burner cut-in / cut-out<br />

• the boiler / flow temperature is outside the band limit<br />

5 ... 6000: Set the desired time.<br />

The upper illustration shows a typical situation for burner step<br />

cut-in after a saving period. The temperature difference between<br />

the desired and the actual boiler / flow temperature is relatively<br />

large, i.e. outside the band limit.<br />

The lower illustration shows a typical situation for burner step<br />

cut-out. The temperature difference between the desired and the<br />

actual boiler / flow temperature is relatively large, i.e. outside the<br />

band limit.<br />

If the ‘Max. T limit’ (ID no. 11049) has been exceeded, the cut-out<br />

of the burner steps takes place every 5 seconds.<br />

Temp.<br />

Temp.<br />

+ +<br />

+<br />

+ + +<br />

Band limit<br />

Desired boiler / flow<br />

temp.<br />

Actual boiler / flow<br />

temp.<br />

Time<br />

Actual boiler / flow<br />

temp.<br />

Band limit<br />

Desired boiler / flow<br />

temp.<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 117<br />

Time