<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

P exercise (pump exercise) 11022<br />

Circuit Setting range Factory setting<br />

1 OFF / ON ON<br />

Exercises the pump to avoid blocking in periods without heat demand.<br />

OFF: The pump exercise is not active.<br />

ON: The pump is switched ON for 1 minute every third day at<br />

noon (12:14 hours).<br />

P frost T 11077<br />

Circuit Setting range Factory setting<br />

1 OFF / -10 ... 20 °C 2 °C<br />

When the outdoor temperature is below the set temperature in ‘P frost T’,<br />

the controller automatically switches ON the circulation pump to protect<br />

the system.<br />

OFF: No frost protection.<br />

-10 ... 20: The circulation pump is ON when the outdoor<br />

temperature is below the set value.<br />

P heat T (heat demand) 11078<br />

Circuit Setting range Factory setting<br />

1 5 ... 40 °C 20 °C<br />

When the desired flow temperature is above the set temperature in ‘P heat T’,<br />

the controller automatically switches ON the circulation pump.<br />

5 ... 40: The circulation pump is switched ON when the desired<br />

flow temperature is above the set value.<br />

P post-run 11040<br />

Circuit Setting range Factory setting<br />

1 0 ... 99 m 3 m<br />

The circulation pump in the heating circuit can be ON for a number of<br />

minutes (m) after heating stop (the desired flow temperature gets lower<br />

than the setting in 'P heat T' (ID no. 11078)).<br />

This function can utilize the remaining heat in e.g. a heat exchanger.<br />

0: The circulation pump stops immediately after the<br />

heating stop.<br />

1 ... 99: The circulation pump is ON for the set time after the<br />

heating stop.<br />

Frost pr. T (frost protection temperature) 11093<br />

Circuit Setting range Factory setting<br />

1 5 ... 40 °C 10 °C<br />

Set the desired flow temperature for example at heating cut-out, total stop<br />

etc. to protect the system against frost.<br />

5 ... 40: Desired frost protection temperature.<br />

Under normal conditions, your system is not frost protected if your<br />

setting is below 0 °C or OFF.<br />

For water-based systems, a setting of 2 °C is recommended.<br />

The valve is fully closed as long as the pump is not switched on.<br />

120 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy