Nz (neutral zone) 12187<br />
Circuit Setting range Factory setting<br />
2 1 ... 9 K 3 K<br />
Set the acceptable flow temperature deviation.<br />
Set the neutral zone to a high value if you can accept a high<br />
variation in flow temperature. When the actual flow temperature<br />
is within the neutral zone, the controller does not activate the<br />
motorized control valve.<br />
Min. act. time (min. activation time gear motor) 12189<br />
Circuit Setting range Factory setting<br />
2 2 ... 50 10<br />
The min. pulse period of 20 ms (milliseconds ) for activation of the gear<br />
motor.<br />
The neutral zone is symmetrical around the desired flow temperature<br />
value, i.e. half the value is above and half the value is below this<br />
temperature.<br />
Setting example Value x 20 ms<br />
2 40 ms<br />
10 200 ms<br />
50 1000 ms<br />
The setting should be kept as high as acceptable to increase the<br />
lifetime of the actuator (gear motor).<br />
<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 137