<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

6.7 Application<br />

ECA addr. (choice of Remote Control Unit) 12010<br />

Circuit Setting range Factory setting<br />

2 OFF / A / B OFF<br />

Decides the communication with the Remote Control Unit.<br />

OFF: No Remote Control Unit. Only room temperature sensor,<br />

if any.<br />

A: Remote Control Unit ECA 30 / 31 with address A.<br />

B: Remote Control Unit ECA 30 / 31 with address B.<br />

Ch.-o. valve / P (changeover valve / pump) 12051<br />

Circuit Setting range Factory setting<br />

2 OFF / ON ON<br />

Choose whether the DHW heating control is based on a changeover valve<br />

or a pump.<br />

OFF: Changeover valve<br />

ON: Pump<br />

Tank, sec. / prim. 12053<br />

Circuit Setting range Factory setting<br />

2 OFF / ON OFF<br />

Choose whether the heating of the DHW tank is dependent on the flow<br />

temperature at S3.<br />

OFF: The DHW tank is heated by means of the S3 temperature.<br />

ON: The DHW tank is heated separately. The S3 temperature<br />

has no influence on the DHW heating.<br />

Circ. P priority 12055<br />

Circuit Setting range Factory setting<br />

2 OFF / ON OFF<br />

Choose whether the DHW circulation pump should be ON during DHW<br />

heating.<br />

OFF: The DHW circulation pump is switched OFF during DHW<br />

heating.<br />

ON: The DHW circulation pump is not switched OFF during<br />

DHW heating.<br />

The Remote Control Unit has no influence on the DHW control.<br />

The Remote Control Unit must be set accordingly (A or B).<br />

When the changeover valve is chosen, pump P1 is ON at heating as<br />

well as at DHW heating demand.<br />

When the pump is chosen, pump P1 is ON at heating and OFF at DHW<br />

heating demand.<br />

When the 'Circ. P priority' is set to OFF, the schedule for the DHW<br />

circulation pump is overruled.<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 139