<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />
DHW P post-run 12041<br />
Circuit Setting range Factory setting<br />
2 0 ... 30 m 0 m<br />
Set the DHW pump (P3) post-run time (minutes). The DHW pump can<br />
continue to be switched ON after the DHW heating procedure in order to<br />
utilize the remaining heat in the heat exchanger / boiler.<br />
0 ... 30: Set the number of minutes for the post-run.<br />
Send desired T 12500<br />
Circuit Setting range Factory setting<br />
2 OFF / ON ON<br />
When the controller acts as a slave controller in a master / slave system,<br />
information about the desired flow temperature can be sent to the master<br />
controller via the <strong>ECL</strong> 485 bus.<br />
OFF: Information about the desired flow temperature is not<br />
sent to the master controller.<br />
ON: Information about the desired flow temperature is sent<br />
to the master controller.<br />
P exercise (pump exercise) 12022<br />
Circuit Setting range Factory setting<br />
2 OFF / ON ON<br />
Exercises the pump to avoid blocking in periods without heat demand.<br />
OFF: The pump exercise is not active.<br />
ON: The pump is switched ON for 1 minute every third day at<br />
noon (12:14 hours).<br />
M exercise (valve exercise) 12023<br />
Circuit Setting range Factory setting<br />
2 OFF / ON OFF<br />
Exercises the valve to avoid blocking in periods without heat demand.<br />
OFF: The valve exercise is not active.<br />
ON: The valve opens for 7 minutes and closes for 7 minutes<br />
every third day at noon (12:00 hours).<br />
In the master controller, 'Demand offset' must be set to a value in order<br />
to react on a desired flow temperature from a slave controller.<br />