02.08.2013 Views

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

Application <strong>A275</strong>.3<br />

Double-insulated (two-chamber) transformer<br />

Terminal Description Max. load<br />

16 Phase for control of circulation pump P4, circuit 2<br />

15 K4 Control of circulation pump ON / OFF, circuit 2 4 (2) A / 24 V a.c.*<br />

14 Phase for control of pumps and burner<br />

13 K3 Control of DHW heating pump ON / OFF, circuit 3 4 (2) A / 24 V a.c.*<br />

12 B1 Burner ON / OFF 4 (2) A / 24 V a.c.*<br />

11 K1 Control of circulation pump ON / OFF, circuit 1 4 (2) A / 24 V a.c.*<br />

10 Supply voltage 24 V a.c. - (SN)<br />

9 Supply voltage 24 V a.c. - (SP)<br />

8 Phase for motorized changeover valve output M1, circuit 3<br />

7 M1 Motorized changeover valve, DHW circuit direction 1 A / 24 V a.c.<br />

6 M1 Motorized changeover valve, heating circuit direction 1 A / 24 V a.c.<br />

5 Phase for motorized control valve M2, circuit 2 1 A / 24 V a.c.<br />

4 M2 Motorized control valve - opening, circuit 2 1 A / 24 V a.c.<br />

3 M2 Motorized control valve - closing, circuit 2 1 A / 24 V a.c.<br />

* Relay contacts: 4 A for ohmic load, 2 A for inductive load<br />

Factory established jumpers:<br />

5 to 8, 9 to 14 , L to 5 and L to 9, N to 10<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 63

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!