<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

Application <strong>A375</strong>.1 (up to 4 burner steps)<br />

Terminal Description Max. load<br />

19 Phase for alarm and burner B4<br />

18 Alarm (A1) 4 (2) A / 230 V a.c.*<br />

17 B4 Burner ON / OFF 4 (2) A / 230 V a.c.*<br />

16 Phase for burner B3<br />

15 B3 Burner ON / OFF 4 (2) A / 230 V a.c.*<br />

14 Phase for pump and burners<br />

13 B2 Burner ON / OFF 4 (2) A / 230 V a.c.*<br />

12 B1 Burner ON / OFF 4 (2) A / 230 V a.c.*<br />

11 P1 Circulation pump ON / OFF 4 (2) A / 230 V a.c.*<br />

10 Supply voltage 230 V a.c. - neutral (N)<br />

9 Supply voltage 230 V a.c. - live (L)<br />

* Relay contacts: 4 A for ohmic load, 2 A for inductive load<br />

Factory established jumpers:<br />

5 to 8, 9 to 14 , L to 5 and L to 9, N to 10<br />

<strong>Danfoss</strong> District Energy VI.GU.L1.02 DEN-SMT/DK 53