02.08.2013 Views

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

ECL Comfort 210/310, A275/A375 Installation Guide - Danfoss ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Installation</strong> <strong>Guide</strong> <strong>ECL</strong> <strong>Comfort</strong> <strong>210</strong> / <strong>310</strong>, application <strong>A275</strong> / <strong>A375</strong><br />

7.0 Settings, circuit 3<br />

7.1 Tank temperature<br />

Charge difference 13193<br />

Circuit Setting range Factory setting<br />

3 1 ... 50 K 15 K<br />

Number of degrees above the desired DHW temperature that will result in<br />

the desired boiler temperature for DHW heating.<br />

1... 50: Number of degrees to be added to the desired DHW<br />

temperature to obtain the desired boiler temperature<br />

for DHW heating.<br />

Start difference 13195<br />

Circuit Setting range Factory setting<br />

3 –50 ... –1 K –3 K<br />

Number of degrees below the desired DHW temperature that will start the<br />

DHW heating.<br />

-50 ... –1: Set the number of degrees.<br />

Temp.<br />

° C<br />

DHW heating<br />

Charge difference<br />

Stop difference<br />

Des. DHW temp.<br />

Start difference<br />

Actual DHW temp.<br />

Time<br />

The desired DHW temperature is related to the tank temperature<br />

sensor.<br />

Example:<br />

Desired DHW temp.: 55 °C<br />

Start difference: -3 K<br />

Result:<br />

The DHW heating starts when the temperature measured by the tank<br />

temperature sensor is lower than 52 °C.<br />

Temp.<br />

° C<br />

DHW heating<br />

Start difference<br />

Desired DHW temp.<br />

DHW temp.<br />

148 DEN-SMT/DK VI.GU.L1.02 <strong>Danfoss</strong> District Energy<br />

Time

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!