9.10 Bus System<br />

Option Profibus DP [OP]<br />

PA<br />

Profibus Address<br />

51<br />

Setting instructions for actuators<br />

including an optional Profibus DP<br />

module – check wiring diagram for<br />

inclusion.<br />

Before setting the parameters for<br />

Option Profibus ensure Remote<br />

Control Source [Od] has been<br />

selected to [oP] in Section 9.7.<br />

(refer to page 42).<br />

Profibus module set-up screens can be<br />

turned off to provide extra security. The<br />

action of turning screens on or off does<br />

not affect its operation.<br />

Use the + or - keys to turn on Profibus<br />

set-up screens.<br />

Profibus set-up screens [On]<br />

PRESS THE<br />

KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

Press the ◗ key to display the Profibus<br />

set-up screens.<br />

The Profibus DP module must be<br />

allocated a unique address.<br />

To set the address the Profibus module<br />

must be isolated from the host by<br />

disconnecting the RS485 highway or<br />

turning off the host device.<br />

Using the + or - keys display the<br />

required address.<br />

Address to be set within the range 01<br />

to 7E Hexadecimal (refer to page 75 for<br />

conversion). If an address value outside<br />

this range is entered, the address set<br />

will revert to 01 (for 00) or 7E (for value<br />

above 7E).<br />

PRESS THE KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

Press the ❖ to display [Pb].