PF<br />

Profibus Remote<br />

Auxiliary Input<br />

53<br />

Rules<br />

1. Function bit set to ‘‘0’’<br />

Any function bit set to ‘‘0’’ indicates that the particular aux input is to be treated as<br />

a digital signal for field status reporting, e.g. a level switch or motor running status.<br />

If the corresponding invert bit is set to a ‘‘0’’, an open contact is reported as a logic<br />

‘‘1’’ and a closed contact is reported as a logic "0" (i.e. this will invert the input).<br />

If the corresponding invert bit is set to a ‘‘1’’, an open contact is reported as a logic<br />

‘‘0’’ and a closed contact is reported as a logic ‘‘1’’ (i.e. this gives a noninverting<br />

input).<br />

2. Function bit set to ‘‘1’’<br />

Any function bit set to ‘‘1’’ indicates that the particular aux input is to be treated as<br />

a digital command to operate the actuator.<br />

When the corresponding invert bit is set to a ‘‘0’’ this represents an N.C. contact as<br />

being the command source, i.e. a closing contact de-energises the input and an<br />

opening contact energises the input.<br />

When the corresponding invert bit is set to a ‘‘1’’, this represents an N.O. contact as<br />

being the command source, i.e. a closing contact energises the input and an<br />

opening contact de-energises the input.<br />

3. ESD Control<br />

When using ESD (aux input 4), the ESD contact mode setting [A2] should be set to<br />

the default value of [nO]. The [A1]–ESD direction setting should be set to either<br />

open or close the valve (refer to page 34).<br />

5. Remote Source Setting [Od]<br />

Ensure that the correct [Od] setting is selected (refer to page 42).<br />

For Profibus this is [OP].<br />

The factory default for [PF] is [OF]<br />

Examples<br />

1. The full range of remote controls is needed. Open and Close are NO and ESD<br />

and Stop/maintain is NC.<br />

Aux I/P 4 3 2 1<br />

Function 1 1 1 1 = F<br />

Invert 0 0 1 1 = 3 i.e. set [PF] to [F3]<br />

2. Open and close control is required along with 2 inverted digital signal inputs.<br />

(Note that with this setting the open and close commands will be maintained.)<br />

Aux I/P 4 3 2 1<br />

Function 0 0 1 1 = 3<br />

Invert 0 0 1 1 = 3 i.e. set [PF] to [<strong>33</strong>]<br />

3. Only an ESD input is needed. The requirement is for push to run control with a<br />

NO contact input.<br />

Aux I/P 4 3 2 1<br />

Function 1 1 0 0 = C<br />

Invert 1 0 0 0 = 8 i.e. set [PF] to [C8]<br />

4. Stop/Maintain Control<br />

When energised this will make the Aux input Open/Close control push to run When<br />

de-energised, the Aux input Open/Close control will be maintained. ESD is always<br />

push to run (non maintained).