Fd<br />

All positioning commands are subject to<br />

a deadband tolerance.<br />

The deadband sets the expected<br />

positioning accuracy of the actuator<br />

and is dependent on various factors<br />

including, actuator output speed,<br />

number of turns and valve torque. If<br />

the deadband is set too low the valve<br />

may ‘‘hunt’’ around the set point.<br />

Use the + or - key to display the<br />

required setting:<br />

[00] to [99] – 0% to 9.9% of valve<br />

stroke.<br />

PRESS THE<br />

Bus System Deadband<br />

Adjustment<br />

2.5% Deadband<br />

KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

Press the ❖ key to display [Ft].<br />

Ft<br />

MIT sets the minimum time between<br />

successive position commands being<br />

actioned. It is used in situations to<br />

reduce the number of starts per hour<br />

and to smooth out fluctuations if<br />

continuous positioning is implemented.<br />

Setting the longest possible time while<br />

maintaining acceptable control will<br />

maximise the life of the motorised<br />

valve.<br />

Use the + or - key to display the<br />

required setting:<br />

[02] to [99] – 2 to 99 seconds.<br />

PRESS THE<br />

Bus System<br />

Motion Inhibit Time (MIT)<br />

5 Second MIT<br />

KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

Press the ❖ key to display [FA].<br />

FA Modbus, Profibus &<br />

DeviceNet<br />

Action on Loss of Signal<br />

Modbus, Profibus & DeviceNet modules<br />

can be set to respond on loss of host<br />

communication by positioning the<br />

valve. Modbus checks for a loss of<br />

general highway communications<br />

whereas Profibus checks for a loss of<br />

communications addressed specifically<br />

to itself.<br />

The default setting is off [OF] and the<br />

default timeout is 255 sec.<br />

Use the + or - key to display the<br />

required setting:<br />

[On] Failsafe determined by setting [FF]<br />

[OF] No failsafe action<br />

PRESS THE<br />

Failsafe Action Enabled<br />

KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

Press the ❖ key to display [FF].<br />

59<br />

FF Modbus, Profibus<br />

& DeviceNet<br />

Failsafe Action<br />

Modbus, Profibus & DeviceNet failsafe<br />

action when [FA] is enabled.<br />

Use the + or - key to display the<br />

required setting:<br />

[Lo] Close valve<br />

[SP] Stay put<br />

[HI] Open valve<br />

PRESS THE<br />

Failsafe Close<br />

KEY.<br />

The displayed option will flash<br />

indicating that it has been set.