H1<br />

Factors Inhibiting<br />

Electrical Operation<br />

Phase<br />

Loss<br />

H1<br />

Position<br />

Error<br />

Local<br />

Controls<br />

Error<br />

Battery Low<br />

on<br />

Power-up<br />

Help Screen 1<br />

POSITION ERROR<br />

Bar ON = Current Position Error<br />

Present.<br />

During power up the actuator position<br />

processor compares the current position<br />

to that stored in the Eeprom. If there is<br />

a discrepancy this is shown as a current<br />

position error.<br />

Re-setting of both actuator limits<br />

should now be carried out (refer to<br />

page 27).<br />

BATTERY LOW ON POWER UP<br />

Bar ON = Low battery detected On<br />

Power Up.<br />

If [OS] is selected [On] (set as default )<br />

the actuator operation will be inhibited<br />

when powered up with a discharged<br />

battery (refer to [OS] page 58).<br />

The battery should be replaced at the<br />

earliest opportunity (refer to page 65).<br />

LOCAL CONTROLS ERROR<br />

Bar ON = Invalid Local Control<br />

Signals Detected.<br />

For example if a Local Open and Close<br />

signal is detected at the same time this<br />

would be classed as an invalid or fault<br />

condition.<br />

PHASE LOSS<br />

Bar ON = Phase Lost (3 Phase<br />

Actuators Only).<br />

Loss of third monitored power supply<br />

phase connected to actuator terminal 3.<br />

H2<br />

Low<br />

Battery<br />

Battery<br />

Discharged<br />

Battery Level and<br />

ESD Control Input<br />

H2<br />

ESD<br />

Active<br />

Help Screen 2<br />

BATTERY DISCHARGED<br />

Bar ON = Battery Discharged.<br />

Bar ON when the battery is no longer<br />

able to support actuator functions<br />

under loss of power conditions.<br />

The battery must be replaced (refer to<br />

Section 10 page 65) and limit positions<br />

reset (refer to [LC] and [LO] page 27).<br />

68<br />

LOW BATTERY<br />

Bar ON = Battery level low.<br />

Bar OFF = Battery OK.<br />

Bar ON when the battery is low but still<br />

able to support the necessary actuator<br />

functions.<br />

The battery should be replaced at the<br />

earliest possible opportunity.<br />

ESD SIGNAL ACTIVE<br />

Bar ON = ESD Signal is present.<br />

When applied, an Emergency<br />

Shutdown Signal will override any<br />

existing local or remote control signal,<br />

causing the actuator to respond in the<br />

direction selected for ESD.<br />

The ESD function will be determined by<br />

the settings on Control Mode<br />

Configuration screens [A1] to [A5]<br />

(refer to Section 9.3 page 34).<br />

The actuator will not respond to any<br />

local or remote control while an ESD<br />

signal is maintained.