Example<br />

Note<br />

9.14 Setting Tool<br />

Local Control [Or]<br />

9.15 Inhibit Operation<br />

After Power Loss [OS]<br />

62<br />

An actuator fitted with the interrupter<br />

timer and set as the example shown in<br />

these instructions would operate at:<br />

Rated speed from full Open to 25%<br />

Open.<br />

1<br />

/6 rated speed from 25% Open to Fully<br />

Closed and from Fully Closed to 25%<br />

Open.<br />

Rated speed from 25% Open to Fully<br />

Open.<br />

With a Folomatic option fitted and the<br />

Interrupter Timer enabled, the<br />

Folomatic Motion Inhibit Timer must be<br />

adjusted to the same time as that set<br />

for the Interrupter Timer “contactor<br />

off”.<br />

Failure to do so will cause the actuator<br />

response to defer to the lower time<br />

which may cause control or process<br />

problems.<br />

For “ON” and “OFF” times in excess of<br />

99 seconds apply to Rotork.<br />

The default setting for Setting Tool<br />

Local Control is [OF].<br />

To enable Setting Tool Control press the<br />

+ or - key to select [On].<br />

PRESS THE<br />

KEY.<br />

The displayed option will flash<br />

indicating that it has been set.<br />

With the red control selector in Local,<br />

the Setting Tool control keys are active<br />

(refer to page 17).<br />

The default setting for this protection option<br />

is disabled [OF]. When disabled it is<br />

important that the actuator is not manually<br />

operated during a power failure if the battery<br />

is low as changes in position cannot be<br />

tracked - refer to page 6 for battery level<br />

status display. Should this occur the limits<br />

must be reset before electric operation takes<br />

place- refer to LC/LO page 27. Locking the<br />

hand auto lever can prevent manual<br />

operation - refer to 3.1 page 2.<br />

Local Setting Tool Control Enabled<br />

Vandal resistant actuators ONLY<br />

(red/black selectors not supplied).<br />

For control, the selection of [Or] is as<br />

follows:<br />

[On] Local Setting Tool control only.<br />

[OF] Local/Remote Control disabled.<br />

[rE] Remote Control only.<br />

The protection may be enabled by using the<br />

+ or - key to select [On]<br />

PRESS THE<br />

KEY.<br />

The displayed option will flash indicating that<br />

it has been set.<br />

When protection is enabled, on power up if a<br />

low battery is detected, the actuator will<br />

inhibit electrical operation and display Power<br />

Loss Inhibit via actuator alarm display (refer<br />

to page 6) and the monitor relay will deenergise.<br />

Limits must reset and the battery<br />

replaced – refer to page 65.