6.2 Application examples<br />

6.2.1 Line-Inverter changeover<br />

Following there is an example describing how <strong>to</strong> switch a mo<strong>to</strong>r from commercial-power operation <strong>to</strong> inverter-operation (and<br />

vice versa) using an internal au<strong>to</strong>matic switch sequence called ISW50 function.<br />

Components needed <strong>to</strong> develop this application:<br />

- Mo<strong>to</strong>r (pump or fan mo<strong>to</strong>r)<br />

- 3 relays (the relays will be connected <strong>to</strong> 3 contac<strong>to</strong>rs)<br />

- 1 thermal relay (optional)<br />

- <strong>FRENIC</strong>-<strong>Eco</strong> inverter (<strong>FRN</strong>-<strong>F1</strong>)<br />

When the primary contac<strong>to</strong>r SW52-1 is opened the inverter will not be powered on. Therefore, and in order <strong>to</strong> keep the<br />

inverter control circuit alive, an auxiliary input voltage is needed from R0/T0 auxiliary input terminals.<br />

Circuit diagram and configuration:<br />

Commercial power contac<strong>to</strong>r<br />

SW88<br />

Inverter primary contac<strong>to</strong>r<br />

SW52_1<br />

Configuration of control circuit:<br />

<strong>FRENIC</strong><br />

<strong>Eco</strong><br />

To switch the mo<strong>to</strong>r from inverter operation <strong>to</strong> commercial-power operation or vice versa the inverter ISW50 function will be<br />

used.<br />

1. DIGITAL INPUTS (in this case FWD, X1 and are used)<br />

- FWD: digital input set as FWD function (RUN command).<br />

- X1: digital input set as mutistep frequency SS1 function (speed).<br />

- X2: digital input set as ISW50 function (<strong>to</strong> switch the mo<strong>to</strong>r).<br />

Thermal relay<br />

Inverter secondary contac<strong>to</strong>r<br />

SW52_2<br />

Chapter 6: Function codes and application example 25