2. DIGITAL OUTPUTS (in this case Y1, Y2 and Y3 are used)<br />
- Y1: digital output set as SW52-1 function (this digital output will be connected <strong>to</strong> relay 1. Relay 1 will open or close<br />
the primary contac<strong>to</strong>r SW52-1).<br />
- Y2: digital output set as SW52-2 function (this digital output will be connected <strong>to</strong> relay 2. Relay 2 will open or close<br />
the secondary contac<strong>to</strong>r SW52-2).<br />
- Y3: digital output set as SW88 function (this digital output will be connected <strong>to</strong> relay 3. Relay 3 will open or close<br />
the commercial power contac<strong>to</strong>r SW88)<br />
RUN command<br />
(FWD)<br />
Speed<br />
ISW50<br />
To switch the mo<strong>to</strong>r<br />
Switching sequence:<br />
FWD<br />
X1<br />
X2<br />
PLC<br />
SOURCE<br />
CMY CM<br />
1. INVERTER OPERATION ------> COMMERCIAL POWER OPERATION<br />
If the digital input set as ISW50 function is changed from ON <strong>to</strong> OFF.....<br />
(1) The inverter output is shut off immediately (IGBT off).<br />
(2) The inverter primary contac<strong>to</strong>r (SW52-1) and the inverter secondary contac<strong>to</strong>r (SW52-2) are opened immediately.<br />
(3) If the RUN command is kept during t1 time (H13 + 0.2 seconds), the commercial power contac<strong>to</strong>r SW88 is closed<br />
and the mo<strong>to</strong>r is switched <strong>to</strong> commercial power operation.<br />
2. COMMERCIAL POWER OPERATION ------> INVERTER OPERATION<br />
Relay 2 (related with SW52-<br />
2 inverter secondary<br />
contac<strong>to</strong>r)<br />
If the digital input set as ISW50 function is changed from OFF <strong>to</strong> ON.....<br />
(1) The primary contac<strong>to</strong>r SW52-1 is closed immediately giving voltage <strong>to</strong> the inverter (inverter is powered).<br />
(2) The commercial power contac<strong>to</strong>r SW88 is opened immediately (disconnecting the mo<strong>to</strong>r from the line).<br />
(3) After t2 time (time required for the inverter main circuit <strong>to</strong> get ready + 0.2 s) the inverter secondary contac<strong>to</strong>r<br />
SW52-2 is immediately closed.<br />
(4) After t3 time (H13 + 0.2 s), the inverter starts driving and the mo<strong>to</strong>r is inverter controlled up <strong>to</strong> the desired<br />
frequency.<br />
Y1<br />
Y2<br />
Y3<br />
Relay 1 (related with<br />
SW52-1 inverter primary<br />
contac<strong>to</strong>r)<br />
Relay 3 (related with<br />
SW88 commercial power<br />
contac<strong>to</strong>r)<br />
Chapter 6: Function codes and application example 26