Timing scheme:<br />

ISW50<br />

COMMERCIAL POWER<br />

INVERTER OPERATION OPERATION<br />

INVERTER OPERATION<br />

Inverter is controlling the mo<strong>to</strong>r<br />

speed<br />

The function codes which have been modified are:<br />

The mo<strong>to</strong>r speed is<br />

fixed <strong>to</strong> commercial<br />

power speed<br />

The inverter starts <strong>to</strong> harmonize the mo<strong>to</strong>r from the<br />

commercial power operation <strong>to</strong> the inverter desired<br />

speed.<br />

Inverter is controlling the mo<strong>to</strong>r<br />

speed<br />

Code Data Description<br />

F02 1 RUN command using terminals (digital inputs)<br />

F03 mo<strong>to</strong>r data Maximum frequency<br />

F04 mo<strong>to</strong>r data Base frequency<br />

F05 mo<strong>to</strong>r data Rated voltage<br />

F07 15 s (for instance) Acceleration time<br />

F08 15 s (for instance) Deceleration time<br />

E01 0 SS1 multistep frequency function assigned <strong>to</strong> X1 terminal (digital input)<br />

E02 40 Switching sequence command ISW50 assigned <strong>to</strong> X2 terminal (digital input)<br />

E20 12 SW52-1 function assigned <strong>to</strong> Y1 terminal (digital output)<br />

E21 13 SW52-2 function assigned <strong>to</strong> Y2 terminal (digital output)<br />

E22 11 SW88 function assigned <strong>to</strong> Y3 terminal (digital output)<br />

E46 1 Language selection (English language selected)<br />

C05 10 Hz (for instance) If X1 terminal is ON, C05 speed will be selected<br />

P01 mo<strong>to</strong>r data Number of mo<strong>to</strong>r poles<br />

P02 mo<strong>to</strong>r data Mo<strong>to</strong>r capacity<br />

P03 mo<strong>to</strong>r data Mo<strong>to</strong>r rated current<br />

P06 mo<strong>to</strong>r data Mo<strong>to</strong>r no load current (for instance 50% of P03). If au<strong>to</strong>tuning mode 2 is done, P06 is au<strong>to</strong> calculated.<br />

H13 2 seconds Restart time<br />