6.2.2 Select Multistep Frequencies (7 different set point frequencies)<br />

To use Multistep Frequencies you have <strong>to</strong> program E01 <strong>to</strong> E05 <strong>to</strong> SS1 (0), SS2 (1) or SS4 (2) functions.<br />

Switching digital input signals (programmed <strong>to</strong> SS1, SS2 and SS4 functions) ON/OFF will switch the frequency command <strong>to</strong><br />

those defined by function codes C05 through C11 (multistep frequencies). With this, the inverter may drive the mo<strong>to</strong>r at 8<br />

different set point frequencies.<br />

The table below lists the frequencies that can be obtained by the combination of switching (SS1), (SS2), and (SS4). In the<br />

"Selected frequency" column, "Other than multistep frequency" represents the set frequencies defined by frequency command<br />

1 (F01), frequency command 2 (C30), or others.<br />

6.2.3 PID Controller<br />

(SS4) (SS2) (SS1) Selected frequency<br />

OFF OFF OFF Other than multistep<br />

frequency<br />

OFF OFF ON C05 (multistep frequency 1)<br />

OFF ON OFF C06 (multistep frequency 2)<br />

OFF ON ON C07 (multistep frequency 3)<br />

ON OFF OFF C08 (multistep frequency 4)<br />

ON OFF ON C09 (multistep frequency 5)<br />

ON ON OFF C10 (multistep frequency 6)<br />

ON ON ON C11 (multistep frequency 7)<br />

In order <strong>to</strong> set up the PID controller the following parameters have <strong>to</strong> be set:<br />

J01. PID control (mode select).<br />

This function is used <strong>to</strong> setup the operation mode of the PID controller. The alternatives are:<br />

0 PID inactive<br />

1 PID active, forward operation<br />

2 PID active, reverse operation<br />

J02. Remote process command.<br />

This parameter is used <strong>to</strong> set the source of the Set Value for the PID Controller.<br />

0 Enable set by Keypad<br />

1 PID process command 1<br />

3 Enable terminal command (up)/(down) control<br />

4 Command via communication link<br />

Chapter 6: Function codes and application example 28