STARTING GUIDE FRENIC-Eco . FRN-F1 - Welcome to Fuji Electric
STARTING GUIDE FRENIC-Eco . FRN-F1 - Welcome to Fuji Electric
STARTING GUIDE FRENIC-Eco . FRN-F1 - Welcome to Fuji Electric
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
9.2 EMC input filter<br />
The following table describes the EMC input filter and the EMC compliance level for each inverter capacity.<br />
Three phase<br />
400 V supply<br />
9.3 DC reac<strong>to</strong>r<br />
Inverter model EMC input filter Compliance level<br />
<strong>FRN</strong>0,75<strong>F1</strong>S-4E FS5536-12-07<br />
<strong>FRN</strong>1,5<strong>F1</strong>S-4E FS5536-12-07<br />
<strong>FRN</strong>2,2<strong>F1</strong>S-4E FS5536-12-07<br />
<strong>FRN</strong>4,0<strong>F1</strong>S-4E<br />
<strong>FRN</strong>5,5<strong>F1</strong>S-4E<br />
FS5536-12-07<br />
FS21312-18-07<br />
C1 conducted (20m, 15kHz); C1 radiated (25m, 15kHz)<br />
<strong>FRN</strong>7,5<strong>F1</strong>S-4E FS5536-35-07<br />
<strong>FRN</strong>11<strong>F1</strong>S-4E FS5536-35-07<br />
<strong>FRN</strong>15<strong>F1</strong>S-4E FS21312-44-07<br />
<strong>FRN</strong>18,5<strong>F1</strong>S-4E FS5536-50-07<br />
<strong>FRN</strong>22<strong>F1</strong>S-4E FS21312-78-07<br />
<strong>FRN</strong>30<strong>F1</strong>S-4E FS21312-78-07<br />
<strong>FRN</strong>37<strong>F1</strong>S-4E FS5536-100-35<br />
<strong>FRN</strong>45<strong>F1</strong>S-4E FS5536-180-40<br />
<strong>FRN</strong>55<strong>F1</strong>S-4E FS5536-180-40<br />
<strong>FRN</strong>75<strong>F1</strong>S-4E FS5536-180-40<br />
<strong>FRN</strong>90<strong>F1</strong>S-4E FS5536-180-40<br />
<strong>FRN</strong>110<strong>F1</strong>S-4E FS5536-250-99<br />
<strong>FRN</strong>132<strong>F1</strong>S-4E FS5536-250-99<br />
<strong>FRN</strong>160<strong>F1</strong>S-4E FS5536-400-99-1<br />
<strong>FRN</strong>200<strong>F1</strong>S-4E FS5536-400-99-1<br />
<strong>FRN</strong>220<strong>F1</strong>S-4E FS5536-400-99-1<br />
<strong>FRN</strong>280<strong>F1</strong>S-4E FN3359-600-99<br />
<strong>FRN</strong>315<strong>F1</strong>S-4E FN3359-600-99<br />
<strong>FRN</strong>355<strong>F1</strong>S-4E FN3359-800-99<br />
<strong>FRN</strong>400<strong>F1</strong>S-4E FN3359-800-99<br />
<strong>FRN</strong>450<strong>F1</strong>S-4E FN3359-800-99<br />
<strong>FRN</strong>500<strong>F1</strong>S-4E FN3359-1000-99<br />
<strong>FRN</strong>560<strong>F1</strong>S-4E FN3359-1000-99<br />
C1 conducted (20m, 15kHz); C2 radiated (25m, 15kHz)<br />
C2 conducted (10m, 10kHz); C2 radiated (10m, 10kHz)<br />
C3 conducted (100m, 6kHz); C2 radiated (100m, 6kHz)<br />
The following table describes the recommended standard DC reac<strong>to</strong>rs for each inverter model.<br />
Three phase<br />
400 V supply<br />
Inverter model Standard DC reac<strong>to</strong>rs<br />
<strong>FRN</strong>0,75<strong>F1</strong>S-4E DCRE4-0,75<br />
<strong>FRN</strong>1,5<strong>F1</strong>S-4E DCRE4-1,5<br />
<strong>FRN</strong>2,2<strong>F1</strong>S-4E DCRE4-2,2<br />
<strong>FRN</strong>4,0<strong>F1</strong>S-4E DCRE4-4,0<br />
<strong>FRN</strong>5,5<strong>F1</strong>S-4E DCRE4-5,5<br />
<strong>FRN</strong>7,5<strong>F1</strong>S-4E DCRE4-7,5<br />
<strong>FRN</strong>11<strong>F1</strong>S-4E DCRE4-11<br />
<strong>FRN</strong>15<strong>F1</strong>S-4E DCRE4-15<br />
<strong>FRN</strong>18,5<strong>F1</strong>S-4E DCRE4-18,5<br />
<strong>FRN</strong>22<strong>F1</strong>S-4E DCRE4-22A<br />
<strong>FRN</strong>30<strong>F1</strong>S-4E DCRE4-30B<br />
<strong>FRN</strong>37<strong>F1</strong>S-4E DCRE4-37B<br />
<strong>FRN</strong>45<strong>F1</strong>S-4E DCRE4-45B<br />
<strong>FRN</strong>55<strong>F1</strong>S-4E DCRE4-55B<br />
Chapter 9: Options<br />
44