R500<br />

2351- 001)<br />

R500 (2351-001)<br />

<strong>TAC</strong> PNEUMODULAR � Integral Relay with Capacity Tank<br />

The integral relay is a modulating device used with<br />

a proportional controller in applications where it is<br />

necessary to maintain the value of a controlled<br />

variable within close limits. Integral action added to<br />

proportional control allows the use of a wider<br />

proportional controller throttling range to avoid<br />

hunting while simultaneously minimizing or<br />

eliminating the offset (of the actual control point<br />

from the desired setpoint) that is inherent in<br />

proportional control alone. When integral action is<br />

added to proportional control, the result is<br />

proportional plus integral control, frequently<br />

referred to as PI control or automatic reset.<br />

Features:<br />

• Provides pneumatic PI (proportional-plus-integral) control,<br />

when used with pneumatic controllers, or<br />

receiver-controllers, having widely adjustable<br />

throttling-range. (Optimum PI control requires adjustable<br />

throttling-range.)<br />

• Has adjustable integral timing, with minutes-per-repeat<br />

scale.<br />

• All ports clearly labeled. Ports align with MCS-S terminals.<br />

• <strong>TAC</strong> PNEUMODULAR: Mounts on MCS-Socket or K502<br />

Mounting Bracket.<br />

Model Chart<br />

Model No.<br />

Wholesale<br />

Model No.<br />

R500 2351-001 a<br />

a Includes plastic mounting strap and adhesive backed mounting base.<br />

Active Connections<br />

Port Connected to<br />

M Main air<br />

B Branch output<br />

S1 Input signal from controller<br />

Connects to K500 capacity tank 20 cubic in.<br />

S2 (328 cubic cm)<br />

Specifications<br />

Construction Glass-filled nylon.<br />

Maximum ambient temperature 140�F (60�C).<br />

Supply air pressure Clean, dry, oil free air required (Ref. EN-123).<br />

Nominal 20 psig (138 kPa).<br />

Maximum 30 psig (207 kPa).<br />

Connections Barbed nipples for 1/4 in. O.D. polyethylene or 5/32 in. I.D. polyurethane tubing.<br />

Air consumption 1728 scim (472 mL/s).<br />

Air flow capacity 230.4 scim. (62.9 mL/s).<br />

Calibration Yes.<br />

Adjustments<br />

Mounting<br />

S2 M<br />

Timing of integral action is adjustable from FAST to OFF, with approximate dial marks of 0.2, 0.3, 0.7,<br />

1.0, 5.0, and 15 minutes.<br />

Designed for use on MCS-S manifold socket. This device can also be field mounted by using the<br />

K502 mounting bracket.<br />

88 © Copyright 2006 <strong>TAC</strong>. All Rights Reserved. F-27383-1<br />

BS1<br />

K500 Capacity Tank<br />

Included with R500

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!