Model Chart (Continued)<br />
Model No. a<br />
Wholesale<br />
Model No. b Model No. a<br />
Wholesale<br />
Model No. b Dial Range<br />
�F (�C)<br />
W/O Dial Limit Stops With Dial Limit Stops<br />
T32-301 2218-132 T32-3011<br />
T12 through T33 Series (2211 through 2218 Series)<br />
2218-142<br />
2218-532 c<br />
T32-321 2218-134 � �<br />
T33-301 2218-133 � �<br />
55 to 85<br />
(13 to 39)<br />
Air<br />
Consumption<br />
31.1 scim<br />
at 16 psig<br />
(8.5 mL/s at<br />
110 kPa)<br />
43.2 scim<br />
at 25 psig<br />
(11.8 mL/s at<br />
172 Kpa)<br />
22.5 scim<br />
at 13 psig<br />
(6.1 mL/s at<br />
90 kPa)<br />
34.5 scim<br />
at 18 psig<br />
(9.4 mL/s at<br />
124 kPa)<br />
29.4 scim<br />
at 15 psig<br />
(8 mL/s at<br />
103 kPa)<br />
34.5 scim<br />
at 20 psig<br />
(9.4 mL/s at<br />
138 Kpa)<br />
Description<br />
(Refer to Following Pages for<br />
More Detail)<br />
Summer-Winter, throttling range<br />
adjustable 2� to 12�.<br />
16 psig Main � R.A., Summer.<br />
25 psig Main � D.A., Winter.<br />
(Can be used with 8 psig summer<br />
main if recalibrated in the field.)<br />
T32-3011 same as T32-301 but has<br />
factory-installed<br />
10-59 setpoint stops.<br />
Summer-Winter Thermostat for use<br />
with Honeywell 13 to 18 psig<br />
Systems.<br />
13 psig Main � R.A., Summer.<br />
18 psig Main � D.A., Winter.<br />
Summer-Winter Thermostat for use<br />
with Johnson main air systems.<br />
25 psig Main � R.A., Summer.<br />
16 psig Main � D.A., Winter.<br />
a All thermostats include: Two mounting screws.<br />
b<br />
All wholesale thermostats include: One or two 1/4 x 3/16 in. tubing reducer(s), 20-693 tubing, 20-714 wall plate, 20-711 mounting plate, and two mounting<br />
screws.<br />
c<br />
This is a thermostat kit; refer to Kit Model Chart on page 122.<br />
Cover Options<br />
Thermostat covers are available in various styles to meet particular requirements. Cover options include models with setpoint<br />
scale and thermometer, setpoint scale only, thermometer only, or blank. An external setpoint adjustment cover is available with<br />
all models and can be field installed on covers where required.<br />
Covers must be ordered separately, refer to Cover Selection Table on page 25.<br />