TK-6xxx Series, TK-8xxx Series<br />

Relay Bulb Thermostats<br />

For proportional temperature control of pneumatic<br />

valves and actuators to maintain air or liquid<br />

temperatures in duct, plenum chambers, liquid<br />

lines, tanks, etc. May also be used as a low limit<br />

thermostat.<br />

Features:<br />

• Two-pipe (Main and Branch) controllers.<br />

• Direct or Reverse Action.<br />

• Liquid-filled sensing elements: Remote-bulb with 6 ft.<br />

(1.8 m) capillary, or 8 ft. (2.44 m) averaging element.<br />

• Field-adjustable throttling range.<br />

Model Chart<br />

Bulb<br />

Model No. Action<br />

Style Dimensions<br />

TK-6024<br />

D.A. a<br />

TK-8024<br />

Straight<br />

Averaging<br />

3/8 x 4-5/8 in. (9.5 x 117 mm).<br />

3/32 in.x 8 ft. (2.4 mm x 2.4 m).<br />

TK-6124<br />

R.A. a TK-8124<br />

Straight<br />

Averaging<br />

3/8 x 4-5/8 in. (9.5 x 117 mm).<br />

3/32 in. x 8 ft. (2.4 mm x 2.4 m).<br />

a Direct Acting (D.A.) � Increase output pressure on temperature rise.<br />

Reverse Acting (R.A.) � Decrease output pressure on temperature rise.<br />

TK-6024 Shown<br />

Specifications<br />

Thermostat Proportional two pipe type. Thermostats are ambient compensated.<br />

Sensing element Remote liquid-filled copper.<br />

Control dial range -20 to 240�F (-29 to 115�C). Shipped as -20 to 120�F, reverse side of dial 100 to 240�F.<br />

Throttling range Adjustable 3 to 35�F/10 psi (2 to 19�C/69 kPa) change in output, factory set at 5�F (3�C).<br />

Output air signal 0.5 psig (3.4 kPa) to supply air pressure -0.5 psig (-3.4 kPa).<br />

Action<br />

Ambient limits<br />

Refer to Model Chart.<br />

Shipping -40 to 150�F (-40 to 65�C). 0 to 98% R.H., non-condensing.<br />

Case operating 40 to 150�F (4 to 65�C). 10 to 98% R.H., non-condensing.<br />

Bulb 310�F (154�C) maximum.<br />

Supply air pressure Clean, oil free, dry air required (reference EN-123).<br />

Nominal 20 psig (138 kPa).<br />

Minimum 15 psig (103 kPa).<br />

Maximum 30 psig (207 kPa).<br />

Air connections 1/8 in. FNPT for main, branches, and AL-362 gages (not included).<br />

Air consumption for sizing air<br />

compressor<br />

13.8 scim (3.8 mL/s).<br />

Air capacity for sizing air mains 16 scim (4.4 mL/s).<br />

Mounting Upright position on a wall or vertical flat surface.<br />

Bulb dimensions Refer to Model Chart.<br />

Capillary length 6 ft. (1.8 m).<br />

Case dimensions 5-13/16 H x 6-3/16 W x 4 D in. (148 x 157 x 102 mm).<br />

150 © Copyright 2006 <strong>TAC</strong>. All Rights Reserved. F-27383-1<br />