R540 (2376-501)<br />
<strong>TAC</strong> PNEUMODULAR � Averaging Relay<br />
The averaging relay is a proportional device<br />
designed for use in pneumatic control systems<br />
where the application requires operation of a final<br />
control device, or some other control action such<br />
as resetting a receiver controller, by the average of<br />
the signals from two pneumatic devices. The relay<br />
also amplifies the volume of air available to the<br />
control device, thereby minimizing system lag.<br />
Features:<br />
• Averaging relay (with adjustable bias, factory set to zero).<br />
Output equals the sum of the two inputs (S-1 and S-2),<br />
divided by two.<br />
• Unlike some competitive bleed-type “averaging relays”<br />
(accurate only when the two inputs are equal, and whose<br />
accuracy decreases as the square of the signal difference),<br />
the R540 is a true averaging relay.<br />
• All ports are clearly labeled. Ports align with MCS-S<br />
terminals.<br />
• <strong>TAC</strong> PNEUMODULAR: Mounts on MCS-Socket or K503<br />
Mounting Bracket.<br />
Model Chart<br />
Model No.<br />
Wholesale<br />
Model No.<br />
R540 2376-501 a<br />
a Includes plastic mounting strap and adhesive backed mounting plate.<br />
Port Connections<br />
Port Connected to<br />
M Main air<br />
B Branch output<br />
S1 Input signal no. 1<br />
S2 Input signal no. 2<br />
Specifications<br />
Action Proportional.<br />
Construction Glass-filled nylon.<br />
Maximum ambient temperature 140�F (60�C).<br />
Supply air pressure Clean, dry, oil free air required (Ref. EN-123).<br />
Nominal 20 psig (138 kPa).<br />
Maximum 30 psig (207 kPa).<br />
Connections Barbed fittings for 1/4 in. O.D. polyethylene or 5/32 in. I.D. polyurethane tubing.<br />
Air consumption 28.8 scim (7.9 mL/s).<br />
Air flow capacity 230.4 scim (62.9 mL/s).<br />
Adjustments<br />
S2 M B S1<br />
Output may be advanced or retarded �10 psig (69 kPa) by means of TOOL-082 (5/64 in. hexhead<br />
wrench).<br />
Mounting<br />
Designed for use on MCS-S manifold socket. This device can also be mounted by using the optional<br />
K502 mounting bracket.<br />
Dimensions 2-1/16 H x 1-7/8 W x 2-33/64 D in. (52 x 48 x 64 mm).<br />