Specifications<br />

Control action Refer to Model Chart.<br />

Construction Glass-filled nylon.<br />

Maximum ambient temperature 140�F (60�C).<br />

Supply air pressure Clean, dry, oil free air required.<br />

Nominal 15 to 25 psig (103 to 172 kPa).<br />

Maximum 30 psig (207 kPa).<br />

Connections Barbed nipples for 1/4 in. O.D. polyethylene tubing.<br />

Air consumption 29 scim(7.9 mL/s).<br />

Air flow capacity 60 scfh (1.7 scmh).<br />

Adjustments<br />

Accessories<br />

Model No. Wholesale Model No. Description<br />

K503 22-151 Optional mounting bracket.<br />

TOOL-082 � 5/64 in. hex wrench.<br />

Typical Applications<br />

Figure 1 R503-1, R503-2 Typical Application.<br />

Figure 2 R503-3 Typical Application.<br />

R503 Series (2353-5xx Series)<br />

Knob operates over two revolutions. A moving pointer slide is provided to indicate both inner and<br />

outer scales.<br />

Mounting<br />

Designed for use on MCS-S manifold socket. These devices can also be surface mounted by using<br />

the K503 mounting bracket.<br />

Dimensions Refer to Model Chart.<br />

Active Connections<br />

Port Description<br />

M Main.<br />

S Signal.<br />

S2 Signal 2 (R503-3 only).<br />

C Common.<br />

NO Normally open.<br />

NC Normally closed.<br />

From Air-Handling Unit<br />

Mixed Air Controller<br />

From Temperature<br />

Controller<br />

M NC NO C S<br />

R503<br />

Diverting Relay<br />

N100-0010<br />

Temperature<br />

Transmitter<br />

located in<br />

Outdoor Air<br />

F-27383-1 © Copyright 2006 <strong>TAC</strong>. All Rights Reserved. 91<br />

M<br />

M<br />

M<br />

M NC NO C S<br />

R503-3<br />

Diverting Relay<br />

S2<br />

To Minimum-Position<br />

Switch for O.A., Return<br />

and Relief DAmpers<br />

To Minimum Position<br />

Switch for Damper Actuators<br />

From Return Air<br />

Enthalpy Transmitter (DA)<br />

From Outdoor Air<br />

Enthalpy Transmitter (DA)