R533 (2373-501)<br />

<strong>TAC</strong> PNEUMODULAR � Multi-Input High and Low Selector<br />

Relay<br />

The selector relay is a device designed for use in<br />

pneumatic control systems where the application<br />

requires the comparison, selection, and<br />

transmission of the highest and/or the lowest of up<br />

to six pneumatic input signals. All input ports are<br />

“dead-ended” and no signal air passes through the<br />

relay to the output ports.<br />

Features:<br />

• Six-input high and low pressure selector. Requires main air<br />

connection.<br />

• Highest of 6 inputs is output at Port H.<br />

• Lowest of 6 inputs is output at Port L.<br />

• Inputs numbered 1 through 6.<br />

• All ports clearly labeled. Ports align with MCS-S terminals.<br />

• <strong>TAC</strong> PNEUMODULAR: Mounts on two MCS-Socket(s) or<br />

on one K502 Mounting Bracket.<br />

Model Chart<br />

Model No.<br />

Specifications<br />

Wholesale<br />

Model No.<br />

R533 2373-501 a<br />

a Includes two plastic mounting straps and adhesive backed mounting plates.<br />

Port Connections<br />

Port Connected to<br />

M Main air<br />

L Lowest branch output<br />

H Highest branch output<br />

1 through 6 Input signals<br />

M 1<br />

2 3 4 5 6 L H<br />

Action Proportional.<br />

Construction Glass-filled nylon.<br />

Maximum ambient temperature 140�F (60�C).<br />

Supply air pressure Clean, dry, oil free air required (Ref. EN-123).<br />

Nominal 20 psig (138 kPa).<br />

Maximum 30 psig (207 kPa).<br />

Connections Barbed fittings for 1/4 in. O.D. polyethylene or 5/32 in. I.D. polyurethane tubing.<br />

Air consumption<br />

Air flow capacity<br />

43 scim (11.8 mL/s).<br />

HI output port 14.4 scim (3.9 mL/s).<br />

LO output port 28.8 scim (7.8 mL/s).<br />

Adjustments None.<br />

Mounting<br />

Designed for use on two MCS-S manifold sockets. This device can also be mounted by using the<br />

optional K502 mounting bracket.<br />

Dimensions 2 H x 4 W x 1-17/64 D in. (51 x 102 x 32 mm).<br />

100 © Copyright 2006 <strong>TAC</strong>. All Rights Reserved. F-27383-1<br />

R533<br />

(2373-501