HKS-8065<br />

HKS-8065<br />

Duct Enthalpy Transmitter<br />

For proportional enthalpy control used with receiver-controller. For<br />

differential enthalpy control, two HKS-8065 are used with AK-52101 to<br />

determine if return or outdoor air has the higher enthalpy. May be used<br />

with receiver-gauges for continuous enthalpy indication at any local or<br />

remote position.<br />

Features:<br />

• Designed to sense total heat (enthalpy) in air ducts.<br />

• Two highly sensitive sensing elements (nylon for relative humidity, bimetal for<br />

temperature) combine to produce 3 to 15 psig (20.7 to 103.4 kPa) output over the<br />

range of 16 to 40 BTU per pound of dry air (37 to 93 kj/kg).<br />

• Sensing element designed for duct insertion.<br />

Model Chart<br />

Model No. Description<br />

HKS-8065 Duct humidity transmitter.<br />

Specifications<br />

Sensing element<br />

Sensing<br />

Combination bimetal/nylon.<br />

Span 24 btu/lb (56 KJ/Kg) dry air.<br />

Range 16 to 40 btu/lb (37 to 93 KJ/Kg) dry air.<br />

Output air signal 3 to 15 psig (21 to 103 kPa).<br />

Action<br />

Ambient limits<br />

Direct.<br />

Shipping -40 to 150�F (-40 to 65�C). 0 to 98% RH, non-condensing.<br />

Operating<br />

-20 to 125�F (-29 to 52�C). 10 to 98% RH, non-condensing. 10 to 2500 fpm (0.05 to 12.7 m/s)<br />

sensed air velocity.<br />

Supply air pressure Clean, oil free, dry air required (reference EN-123).<br />

Nominal 20 psig (138 kPa) through 0.0075 in. (190 �m) restrictor.<br />

Minimum 18 psig (124 kPa).<br />

Maximum 30 psig (207 kPa).<br />

Air connections Barbed for 1/4 in. O.D. plastic tube.<br />

Air consumption for sizing air<br />

compressor<br />

41.5 scim (11.3 mL/s) at 20 psig (138 kPa) supply through a 0.0075 in. (190 �m) restrictor.<br />

Air capacity for sizing air mains 48 scim (13.2 mL/s) when supplied by a 20 psig (138 kPa) supply air.<br />

Mounting Duct.<br />

Dimensions<br />

4-3/16 H x 4 W x 4 D in. (106 x 102 x 102 mm); tube mounting hole diameter is 1-3/8 in. (35 mm) and<br />

tube insertion length is 4-1/4 in. (108 mm).<br />

Accessories<br />

Model No. Description<br />

AT-532-098-1-1 0.0075 restrictor (white).<br />

AT-532-098-1-2 0.005" restrictor (Red).<br />

AT-532-098-1-3 0.010" restrictor (Blue).<br />

AT-533-67 Adaptor 1/4 in. plastic tubing to 3/16 in. copper or 1/4 in. copper with 1/4 in. solder coupling (not included).<br />

Typical Applications<br />

1 2<br />

M<br />

S<br />

HKS-8065<br />

Duct Enthalpy Transmitter<br />

1 1000 ft. (305m) max. between<br />

gauge and transmitter.<br />

2 200 ft. (61m) max. between<br />

restrictor and transmitter.<br />

Figure 1 Typical Application.<br />