Accessories<br />

Model No. Wholesale Model No. Description<br />

K502 22-150 Optional mounting bracket.<br />

Typical Applications<br />

2<br />

1<br />

2<br />

3<br />

Zone 4 Thermostat<br />

(Typical) D.A. Damper Motor<br />

(Typical)<br />

M M B<br />

Zone 4<br />

Zone Damper (Typical)<br />

M<br />

Zone<br />

1<br />

Zone<br />

2<br />

Zone<br />

3<br />

M 1 2 3 4 5 6 L<br />

Hot Deck: N.O.<br />

Cold Deck: N.C.<br />

R533<br />

High/Low Selector Relay<br />

If all 6 inputs are not used, and if the low (L) output is used,<br />

connect the last used input to the remaining unused inputs.<br />

This keeps the low (L) output from reading "zero".<br />

If only the high (H) output is used, it is not necessary to<br />

connect the unused inputs.<br />

If either output (L or H) must operate valve or damper<br />

actuators, use an R532-L volume-booster relay to<br />

increase air capacity for that output on a 1:1 basis.<br />

Figure 1 Typical Application.<br />

R533 (2373-501)<br />

F-27383-1 © Copyright 2006 <strong>TAC</strong>. All Rights Reserved. 101<br />

H<br />

1<br />

To Hot Deck Controller Reset 3<br />

To Cold Deck Controller Reset