T460 Series (2298 Series)<br />

Unit Temperature Controllers<br />

The Unit Temperature Controllers are designed for<br />

the proportional control of pneumatic devices and<br />

actuators in environmental control systems. These<br />

devices are designed primarily as return air<br />

controllers in induction units, fan coil units, and<br />

unit ventilators.<br />

Features:<br />

• Small size.<br />

• Attractive appearance.<br />

• Stable, linear response to room temperature changes.<br />

• Sensor may be mounted up to 200 ft. (61 m) from<br />

controller; connects to controller body with 1/4 in. outside<br />

diameter (O.D.) polytube.<br />

• Summer-winter models have snap-acting changeover from<br />

direct action to reverse action and vice versa.<br />

Model Chart<br />

Model No.<br />

Wholesale Model<br />

No.<br />

T460-301 2298-060a a Includes mounting bracket.<br />

Specifications<br />

Action Comments<br />

Reverse acting at 16 psig, direct acting at 25 psig<br />

T461-301 2298-061a Direct<br />

T462-301 2298-062a Reverse<br />

T463-301 2298-063a Direct acting at 16 psig, reverse acting at 25 psig<br />

Setpoint range 65 to 85�F.<br />

Throttling range 4�F fixed.<br />

Sensitivity 2.5 psig/�F fixed.<br />

Maximum ambient temperature 140�F (60�C).<br />

Main air pressure Clean, dry, oil free air required (Refer to EN-123).<br />

Nominal<br />

T460-301: 16 psig reverse acting, 25 psig direct acting.<br />

T461-301, T462-301: 20 psig.<br />

T463-301: 16 psig direct acting, 25 psig reverse acting.<br />

Maximum 30 psig.<br />

Connections<br />

Air consumption<br />

Fittings for 1/4 in. O.D. plastic tubing.<br />

T460-301, T463-301 29.4 scim (8.0 mL/s) at 16 psig, 45 scim (12.3 mL/s) at 25 psig.<br />

T461-301, T462-301 29.4 scim (8.0 mL/s) at 16 psig.<br />

Adjustments External or concealed.<br />

Calibration point Factory calibrated at 9 psig for T461 and T462; 12 psig for T460 and T463.<br />

Mounting Using the mounting bracket, purchased separately, or wall mounting.<br />

Dimensions 2-1/32 H x 2-1/32 W x 1-3/8 D in. (52 x 52 x 35 mm).<br />

Includes metal cover and remote<br />

bimetal sensor.<br />

134 © Copyright 2006 <strong>TAC</strong>. All Rights Reserved. F-27383-1<br />

T460<br />

Series<br />

(2298<br />

Series)