14.11.2012 Views

TAC Pneumatic Products Catalog

TAC Pneumatic Products Catalog

TAC Pneumatic Products Catalog

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Specifications (Continued)<br />

Mounting<br />

HKS-2033 Duct.<br />

HKS-5033 Wall (has beige plastic cover).<br />

Dimensions<br />

HKS-2033<br />

HKS-5033<br />

HKS-2033, HKS-5033<br />

Accessories<br />

Model No. Description<br />

AKS-1189 Accessory scale plate, +/- 8% RH for HKS-2033, HKS-5033.<br />

AKS-1199 Accessory scale plate, +/- 2” water for HKS-2033, HKS-5033.<br />

AT-504 Plaster hole cover (small).<br />

AT-505 Surface mounting base.<br />

AT-506 <strong>Pneumatic</strong> wall box fitting (two tubes) used for mounting AT-532-111-1-01 under cover of HKS-5033.<br />

AT-532-098-1-1 0.0075 restrictor (white).<br />

AT-532-098-1-2 .005" restrictor (Red).<br />

AT-532-098-1-3 .010" restrictor (Blue).<br />

AT-532-111-1-01 0.0075 tee restrictor for 5/32 in. plastic tubing.<br />

AT-532-111-1-03 0.010 tee restrictor for 5/32 in. plastic tubing.<br />

AT-533-67 Adaptor 1/4 in. plastic tubing to 3/16 in. copper or 1/4 in. copper with 1/4 in. solder coupling (not included).<br />

AT-533-101 Adaptor 1/4 in. plastic to 5/32 in. plastic.<br />

AT-533-127 Adaptor 3/16 in. copper or 1/4 in. copper with 1/4 in. solder coupling (not included) to 5/32 in. plastic.<br />

AT-533-129 5/32" x 5/32" Barbed brass connector.<br />

Typical Applications<br />

S<br />

HKS-2033, Duct<br />

Transmitter<br />

HKS-5033 Room<br />

Transmitter<br />

4-3/16 H x 4 W x 2-1/16 D in. (106 x 102 x 52 mm); tube mounting hole diameter is 1-3/8 in. (35 mm)<br />

and tube insertion length is 4-1/4 in. (108 mm).<br />

4-3/8 H x 2-3/4 W x 1-5/8 D in. (111 x 70 x 43 mm). Order fittings separately for type of wall<br />

construction.<br />

N100-0010<br />

M<br />

B M S R C<br />

Receiver Controller<br />

(Reverse Acting)<br />

Figure 1 Typical Application.<br />

M NC NO C S<br />

R527 Series E/P Relay<br />

N.C. Steam Valve<br />

8-13 psig<br />

F-27383-1 © Copyright 2006 <strong>TAC</strong>. All Rights Reserved. 39<br />

STM.<br />

M M<br />

1 HKS-2033 is usually located in the return (or exhaust) air duct, to measure<br />

space relative humidity.<br />

2 HKS-5033 is wall mounted, in the room, to measure area relative humidity.<br />

3 When the air-handling unit fan motor is de-energized, the E/P relay removes<br />

control air from the normally closed steam valve, closing it fully.<br />

V<br />

Vac Wire to<br />

Fan Starter<br />

To Steam<br />

Humidifier