N100-4017 (2364-202)<br />

Low Differential <strong>Pneumatic</strong>-Electric Switch<br />

The pneumatic-electric switch features a SPDT<br />

narrow differential switch which makes it suitable<br />

for use with wide span pneumatic transmitters in<br />

such applications as alarm initiation and outdoor<br />

changeover of heating and cooling functions.<br />

Features:<br />

• Narrow-differential P.E. switch can be used with any type of<br />

pneumatic transmitter to initiate an alarm caused by either<br />

a high or low alarm condition.<br />

• May be wall-mounted or panel-mounted where necessary<br />

to keep wiring runs short.<br />

Model Chart<br />

Model No.<br />

Wholesale<br />

Model No.<br />

N100-4017 2364-202 Low differential pneumatic-electric switch.<br />

Specifications<br />

Typical Applications<br />

Figure 1 Typical Application.<br />

Description<br />

Setpoint Adjustable fro 3 to 30 psig (21 to 207 kPa).<br />

Switch action SPDT.<br />

Switch rating 5A at 125 to 250 Vac.<br />

Differential Non-adjustable, 0.25 psig (1.7 kPa) (lowest setpoint) to 0.7 psig (3.4 kPa) (highest setpoint).<br />

Air signal pressure Clean, dry, oil free air required (refer. EN-123).<br />

Maximum overpressure<br />

Connections<br />

200 psig (1380 kPa) above setpoint.<br />

Air 1/8 in. MPT.<br />

Electrical<br />

Environment<br />

Coded screw terminals.<br />

Locations NEMA 1.<br />

Case 1/2 in. conduit connection.<br />

Mounting Wall or panel.<br />

Dimensions 4-3/8 x 3-1/2 x 2-13/16 in. (111 x 39 x 71 mm).<br />

Transmitter<br />

N4-32<br />

M<br />

N100-4017<br />

66 © Copyright 2006 <strong>TAC</strong>. All Rights Reserved. F-27383-1<br />

C<br />

NO<br />

Wire to initiate alarm<br />

on temperature increase<br />

N100-401<br />

(2364-202