S510, S511 Series (2390 Series)<br />

Specifications (Continued)<br />

Connections Barbed fittings for 1/4 in. O.D. polyethylene or 5/32 in. I.D. polyurethane tubing.<br />

Air consumption 28.8 scim (7.9 mL/s).<br />

Air capacity 230.4 scim (62.9 mL/s).<br />

Mounting<br />

Dimensions<br />

Designed for use on MCS-S manifold socket. These devices can also be mounted on a panel face or<br />

surface mounted by using the appropriate mounting bracket (refer to Accessories).<br />

S510 2-1/16 H x 1-7/8 W x 3-1/4 D in. (52 x 48 x 83 mm).<br />

S511-5, S511-10 2-1/16 H x 1-7/8 W x 3-1/2 D in. (52 x 48 x 89 mm).<br />

Dial Plates for S510, S511-5, and S511-10<br />

Model No.<br />

Wholesale<br />

Model No.<br />

50-01 22-301 Warmer, arrow � clockwise.<br />

50-02 22-302 Warmer, arrow � counterclockwise.<br />

50-03 22-303 Increase, arrow � clockwise.<br />

50-04 22-304 Increase, arrow � counterclockwise.<br />

50-05 22-305 0 to 100.<br />

50-06 22-306 Blank.<br />

50-51 22-351 10 divisions.<br />

50-53 22-353 0 to 20 psig.<br />

Accessories<br />

Model No. Wholesale Model No. Description<br />

50-xx � Dial Plates (refer to Dial Plates for S510, S511-5, and S511-10 Table).<br />

TOOL-082<br />

Mounting Brackets<br />

� 5/64 in. hexhead wrench.<br />

K511 22-155 Single switch bracket.<br />

K512 22-156 One switch and one 2 in. gauge bracket.<br />

K514 22-157 Two switches and two 2 in. gauge brackets.<br />

Typical Applications<br />

114<br />

Branch Air to<br />

Control Device<br />

M<br />

M<br />

N100-0010<br />

B M S R C<br />

P541<br />

Receiver Controller (DA)<br />

To E/P Relay and<br />

Damper Actuators<br />

S511 Gradual Switch<br />

Damper Minimum Position<br />

Dial Markings<br />

M B<br />

S510<br />

Gradual Switch<br />

Figure 1 S510 Typical Application.<br />

Figure 2 S511 Series Typical Application.<br />

M<br />

Temperature<br />

Transmitter<br />

(3-15 psig)<br />

N100-0010<br />

Temperature<br />

Transmitter<br />

M B S1 B M S R C<br />

(3-15 psig)<br />

P541<br />

Receiver Controller (DA)<br />

M<br />

M M<br />

© Copyright 2006 <strong>TAC</strong>. All Rights Reserved. F-27383-1