B<br />

Motor Protection<br />

Tripping times for ZEV electronic motor-protective relay<br />

Tripping class, can be selected 5 10 15 20 25 30 35 40<br />

Tripping time in s (± 20 %) With 3-pole symmetric loading from cold state<br />

Setting current IE x 3 11.3 22.6 34 45.3 56.6 67.9 79.2 90.5<br />

Recovery time after trip<br />

x 4 8 15.9 23.9 31.8 39.8 47.7 55.7 63.6<br />

x 5 6.1 12.3 18.4 24.6 30.7 36.8 43 49.1<br />

x 6 5 10 15 20 25 30 35 40<br />

x 7.2 4.1 8.2 12.3 16.4 20.5 24.5 28.6 32.7<br />

x 8 3.6 7.3 10.9 14.6 18.2 21.9 25.5 29.2<br />

x 10 2.9 5.7 8.6 11.5 14.4 17.2 20.1 23<br />

Class 5 10 15 20 25 30 35 40<br />

trecovery after overload trip [min] 5 6 7 8 9 10 11 12<br />

trecovery after test button trip [sec] 5 5 5 5 5 5 5 5<br />

Tripping characteristics:<br />

These tripping characteristics are mean values of the spread at 20°C<br />

ambient temperature in a cold state. Tripping time depends on response<br />

current. With devices at operating temperature, the tripping<br />

time of the overload relay reduces to approximately 25% of the read<br />

off value.<br />

Thermistor tripping<br />

Rated trip resistance R = 3200 Ω ± 15%<br />

Recovery resistance R = 1500 Ω ± 10%<br />

Total PTC thermistor resistance ∑ RK ≤ 1500 Ω<br />

at RK ≤ 250 Ω per sensor: 6 sensors<br />

at RK ≤ 100 Ω per sensor: 9 sensors<br />

Ready to respond after trip at 5 °C under response temperature<br />

B22 moellerNA.com STARTER-CAT-USA-1206<br />

Seconds Minutes<br />

2h<br />

100<br />

15<br />

10<br />

5<br />

2<br />

1<br />

ZEV 3-pole<br />

CLASS 40<br />

35<br />

30<br />

25<br />

20<br />

20<br />

10<br />

7<br />

15<br />

5 10<br />

3<br />

CLASS 5<br />

2<br />

11<br />

2 3 4 5 6 78910 x Setting current<br />

Electronic Overload Relays<br />

With a phase failure<br />

or unbalance > 50%,<br />

the ZEV will trip<br />

<strong>with</strong>in 2.5 seconds.<br />

EC prototype test certification number:<br />

ZEV PTB 01 ATEX 3233<br />

Selection Aids<br />

For protection of motors in EEx e area, also order AWB2300-1433G<br />

“ZEV motor-protective system, Overload monitoring of motors in<br />

EEX e areas”.<br />